6.2

Enable communication

Communication is active when:
• The device has a valid device address.
• A bus power supply is available.
• The device is not in the Commissioning menu.
6.2.1

"Communication" submenu

See basic documentation P3127, "Communication via KNX bus", for a detailed
description of communications. You must have basic knowledge of device addresses
and network topologies.
Main menu > Commissioning > Communication
Operating line
Area
Line
Device address
Search address
Programming mode
Setting values Area, Line and Device address allow for defining individual device
addresses.
Automatic address searches are triggered via operating line Search address. Successful
address searches are acknowledged with status Address found. Status Address failed
means that the address search was unsuccessful.
Programming mode must be set to On to allocate addresses in ETS. ETS automatically
resets the value to Off after successful address allocation.
• If a higher line coupler in the network topology supplies SNA information different
from the values set for area and line, the line coupler's values are assumed.
• An error message is triggered if the device address for 2 devices is identical.
6.3

Device list

The list of operable bus devices is referred to as Device list. The menu tree of the bus
device is opened from the bus operator unit's device list.
Bus devices not listed in the device list cannot be operated using the bus operator unit.
Bus devices are listed as follows in the device list:
Bus operator unit RMZ792 Series B
6 "Commissioning" menu
Range
0...15
0...15
1...255
--- / Address found
Off / On
Factory setting
0
2
255
---
Off
CE1P3113en
07.07.2011