Analog value representation

B.1
Analog value representation in the current measurement range 0
to 20 mA
Display / current measuring range 0 to 20 mA
Values
Dec.
Hex.
32512
32511
...
27649
27648
...
614
613
...
1
0
1
Substitute value 0 and QI = 0 is provided by the F-module. In S7 F/FH systems, the substitute
value is output as configured at the SUBS_V input of the F-channel driver.
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA
Current measuring
range
0 to 20 mA
7F00
>23.518 mA Overflow
7EFF
23.518 mA Overrange
...
6C01
20.007 mA
6C00
...
266
0.4442 mA
265
<0.4442 mA Wire break
...
1
723.4 nA
0
Ranges
1
...
20 mA Nominal range
...
1
...
0 mA
B
Diagnostic message
Overflow
-
-
Wire break
109