Supplementary system components
6.3 TB30 terminal board
Note
With momentary interruptions in the 24 V supply, the digital outputs are deactivated during
this time.
6.3.3.5

Analog inputs and outputs

Table 6- 7
Terminal block X482
Terminal
1
2
3
4
5
6
7
8
Table 6- 8
Characteristics
Connectable cable types
Stripped length
Tool
Note
An open input is interpreted as approximately "0 V".
The power supply of the analog inputs/outputs of the TB30 is via the option slot of the
D4x5-2 control unit and not via X424.
The shield is connected to the control unit. For further information on "Creating a shield
connection", see
Section "Connecting".
90
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
AO 0+
AO 0-
AO 1+
AO 1-
X482 wiring
Rigid
Flexible
Flexible, with wire-end ferrule without plastic sleeve
AWG / kcmil
SIMOTION D4x5-2
Technical specifications
Analog inputs (AI):
Voltage: -10 V to +10 V
Internal resistance: 65 kΩ
Resolution: 13 bits + sign
Analog outputs (AO):
Voltage range: -10 V to +10 V
Load current: max. -3 mA to +3 mA
Resolution: 11 bits + sign
Sustained short-circuit strength
Type
Conductor cross-sections
0.14 mm
0.14 mm
0.25 mm
26 to 20
8 to 9 mm
Screwdriver 0.4 x 2.0 mm
Commissioning and Hardware Installation Manual,
to 0.5 mm
2
2
to 0.5 mm
2
2
to 0.5 mm
2
2
SIMOTION D4x5-2
Manual, 11/2010