Analog Inputs And Outputs - Siemens SIMOTION D4 5-2 Series Manual

Hide thumbs Also See for SIMOTION D4 5-2 Series:
Table of Contents

Advertisement

Supplementary system components
6.3 TB30 terminal board
6.3.3.5

Analog inputs and outputs

Table 6- 8
Table 6- 9
Characteristics
Connectable conductor types
- Rigid
- Flexible
- Flexible with end sleeve, without plastic sleeve
- AWG/kcmil
Stripped length
Tool
Max. cable length
Note
An open input is interpreted as approximately "0 V".
The power supply of the analog I/Os of the TB30 is via the option slot of the D4x5-2 control
unit and not via X424.
The shield is connected to the control unit. For further information concerning "Establishing a
shield connection", refer to the
Manual, "Connecting I/Os" section.
CAUTION
The common-mode range must not be infringed.
The analog differential voltage signals can have a maximum offset voltage of ±30 V with
respect to the ground potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
104
Terminal block X482
Terminal
1
2
3
4
5
6
7
8
X482 wiring
SIMOTION D4x5-2
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
AO 0+
AO 0-
AO 1+
AO 1-
Type
Conductor cross-section
0.14 mm
to 0.5 mm
2
0.14 mm
to 0.5 mm
2
0.25 mm
to 0.5 mm
2
26 to 20
8 to 9 mm
Screwdriver 0.4 x 2.0 mm
30 m
Commissioning and Hardware Installation
2
2
2
SIMOTION D4x5-2
Manual, 02/2012

Hide quick links:

Advertisement

Table of Contents
loading