Parameters
2.2 Parameter description
2.2.5

Option handling: Slot 2 to 63 (with RESERVE module)

45B
This parameter can be used to enable or disable checking of the configuration.
● Slots 2 to 63 are enabled: Instead of the configured electronic module you can also insert
a RESERVE module into the relevant slot without generating a diagnostics message.
● Slots 2 to 63 are disabled: Only the configured module can be located on the relevant
slot. RESERVE modules are treated as incorrect modules. Depending on the setting of
the "Enable startup for set <> actual configuration" parameter, the ET 200S will either
terminate or continue data exchange.
2.2.6

Diagnostic interrupt

46B
This parameter can be used to enable or disable diagnostic interrupts. Diagnostic interrupts
are supported
● on PROFIBUS DP, if the ET 200S is in DPV1 mode.
2.2.7

Process interrupt

47B
This parameter can be used to enable or disable process interrupts. Process interrupts are
supported.
● On PROFIBUS DP, if the ET 200S is in DPV1 mode.
2.2.8

Insert/remove-module interrupt

48B
This parameter can be used to enable or disable remove/insert module interrupts.
Remove/insert module interrupts are supported
● On PROFIBUS DP, if the ET 200S is in DPV1 mode.
2.2.9

Analog-value format

49B
You set the number format for all analog electronic modules here.
2.2.10

Interference frequency suppression

50B
The frequency of your AC power system can interfere with the measured value especially
when measuring in low voltage ranges and using thermocouple elements. Enter the line
frequency for your system here (50 Hz or 60 Hz).
The interference frequency suppression parameter applies to all analog electronic modules.
This parameter is also used to specify the integration and conversion time of the various
modules. See the technical data for the analog electronic modules.