Emergency Stop Category 1; 230 V Ac (Option L59) - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.11 Other connections
4.11.13

EMERGENCY STOP category 1; 230 V AC (option L59)

Description
EMERGENCY STOP category 1 for controlled stopping according to EN 60204-1. This
function stops the drive by means of a quick stop along a deceleration ramp that must be
parameterized. The cabinet unit is then disconnected from the power supply via the line
contactor, while bypassing the electronics by means of a safety combination (according to
EN 60204-1).
The operating state and the function are indicated by eight LEDs (-K120, -K121).
Connecting
Table 4- 47
Terminal
1)
Max. connectable cross-section: 4 mm²
Setting
The time (0.5 to 30 s) set for the contactor safety combination (-K121) should be longer than
(or at least equal to) the time that the drive requires to reach a standstill via the quick stop
(OFF3 ramp-down time, p1135), as the converter is disconnected from the power supply
when the time expires (at -K121).
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs on -K120, -
K121) are described in the "Additional Operating Instructions" of the Operating Instructions.
138
Terminal block X120 – connection for EMERGENCY STOP category 1 (230 V AC)
4
5
7
8
9
10
11
14
12
13
15
16
17
18
NO: NO contact
Technical data
Jumper wired in the factory
Loop in EMERGENCY OFF button from line side,
remove jumpers 7-8 and connect button
Jumper wired in the factory
Jumper wired in the factory
Jumper wired in the factory
"On" for monitored start:
Remove jumpers 15–16 and connect button.
NO
: Checkback "trip safety combination"
1)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A