X533 - Safe stop
option
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
www.aotewell.com
The safe stop option comprises the safety relay and the connecting
terminals for relay triggering and a checkback contact.
Terminal
Designation
1
Contact 1
2
Contact 2
3
Control input
"safe stop"
4
P24 DC
Connectable cross-section: 1.5 mm² (AWG 16)
Terminal 4 is at the front when installed.
Table 7-20

Terminal assignment for the "safe stop" option

The field coil of the safety relay is connected at one end to the
grounded electronics frame. When the field coil is supplied via an
external 24 V supply, its negative pole must be connected to ground
potential. The external 24 V supply must comply with the requirements
for PELV circuits to EN 50178 (DIN VDE 0160).
In the shipped state, a jumper is inserted between terminals 3 and 4.
The jumper must be removed before the "SAFE STOP" function can be
used and an external control for selecting the function connected.
If the safety relay is supplied via the internal supply at X533:4, the
external 24 V supply must deliver at least 22 V at terminal X9:1/2 to
ensure that the relay picks up reliably (internal voltage drop).
Terminal strip
- X533
1
2 3
P15
Optocoupler /
fibre optics
supply
Operating Instructions
sales@aotewell.com
Meaning
Checkback "safe stop"
Checkback "safe stop"
Rated resistance of field coil
≥ 823 Ω ± 10 % at 20 °C
Supply voltage "safe stop"
4
Industry Automation
Connecting-up
Range
DC 20 V – 30 V
1 A
DC 20 V – 30 V
max. operating
frequency: 6/min
DC 24 V /
30 mA
7-19