Bi: No Quick Stop / Quick Stop (Off3) Signal Source 1; Bi: No Quick Stop / Quick Stop (Off3) Signal Source 2 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
CAUTION
When "master control from PC" is activated, this binector input is effective.
p0848[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the first signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switching on inhibited)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- no OFF3 (enable is possible)
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0849[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 2 / OFF3 S_src 2
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the second signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switching on inhibited)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- no OFF3 (enable is possible)
CAUTION
When "master control from PC" is activated, this binector input is effective.
p0849[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 2 / OFF3 S_src 2
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T
Unit group: -
Min:
-
450
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
4022.2
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents