• Excepting customized texts, all operating texts are displayed in the language set on
the bus operator unit regardless of the settings on the various bus devices.
• Exception: Customized texts and fault texts from other bus devices are displayed
as is.
• Heterogeneous language settings for bus operator unit and bus devices may result
in unintelligible, erroneous text display. Use the same language setting within the
entire, operated plant.
• The bus operator unit also allows you to change the language settings of the KNX
device. Use the device list to set the language in the bus device's menu. If you select
a language not available in the bus device, the bus device selects English as default
language.
8.3

Select temperature unit

You can select the temperature unit for the bus operator unit as °C or °F.
Main menu > Settings > Device
Operating line
Unit
Temperatures are displayed in the unit selected on the bus operator unit regardless
of the settings on the various bus devices.
8.4

Operator unit display contrast

The display contrast can be adapted to the current environment.
Main menu > Settings > Device
Operating line
Contrast
8.5

Display bus fault status messages

The following parameter determines the fault status messages to be displayed in the
menu or Info page Fault status message bus.
Main menu > Settings > Faults
Operating line
Fault status message bus
• Device list only:
Fault status messages are displayed only by devices on the device list.
• All device:
Fault status messages are displayed for all KNX network devices.
Faults from devices not on the device list can neither be acknowledged nor reset.
In addition, they are not indicated on the fault LED.
Bus operator unit RMZ792 Series B
8 General settings
Range
°C / °F
Range
0...100%
Range
Device list only / All
devices
Factory setting
°C
Factory setting
50%
Factory setting
Device list only