9.6

Alarm, fault, and system events for compartment identification

Messages
Table 9- 1
Alarm, fault, and system events
Message
Initialization module write-protected
Initialization module write-protected,
parameter changes not allowed
Initialization module identification data
write-protected
Initialization module read in
Initialization module programmed
Initialization module cleared
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
9.6 Alarm, fault, and system events for compartment identification
Description
The initialization module is completely
write-protected.
The initialization module is completely
or partially write-protected.
Reparameterization of SIMOCODE pro
is denied because the initialization
module is write-protected.
The device addressing and the I&M
data in the initialization module are
write-protected. Parameterization will
only be accepted by SIMOCODE if the
new parameter set is identical to the
data stored in the initialization module
at that time.
The parameters of the initialization
module were read into SIMOCODE.
The reparameterization was accepted
in the initialization module.
The initialization module has been
cleared and is now back in the as-
delivered condition.
Compartment identification
Troubleshooting
Deactivate write protection of the
initialization module.
Deactivate write protection of the
initialization module.
Select a parameterization with
identical addressing and I&M data
Deactivate the partial write
protection of the initialization
module.
-
-
-
171