when a short-circuit occurs. To ensure safe use, exercise extra caution when
installing and placing the breaker. Follow the manufacturer's instructions.
To ensure safety, you can configure an electromagnetic contactor on the input side to control the
switch-on and switch-off of the main circuit power, so that the input power supply of the VFD can be
effectively cut off when a system fault occurs.
VFD model
GD350-19-1R5G-4-B
GD350-19-2R2G-4-B
GD350-19-004G-4-B
GD350-19-5R5G-4-B
GD350-19-7R5G-4-B
GD350-19-011G-4-B
GD350-19-015G-4-B
GD350-19-018G-4-B
GD350-19-022G-4-B
GD350-19-030G-4-B
GD350-19-037G-4-B
GD350-19-045G-4-B
GD350-19-055G-4-B
GD350-19-075G-4-B
GD350-19-090G-4-B
GD350-19-110G-4-B
GD350-19-132G-4
GD350-19-160G-4
GD350-19-185G-4
GD350-19-200G-4
GD350-19-220G-4
GD350-19-250G-4
GD350-19-280G-4
GD350-19-315G-4
GD350-19-355G-4
GD350-19-400G-4
GD350-19-450G-4
GD350-19-500G-4
Note: The accessory specifications described in the preceding table are ideal values. You can
select accessories based on the actual market conditions, but try not to use those with lower
Table D-3 AC 3PH 380V(-15%) – 440V(+10%)
Fuse (A)
10
10
20
35
40
50
60
70
90
125
125
150
200
250
300
350
400
500
600
600
700
800
1000
1000
1000
1200
1200
1400
Breaker (A)
6
10
20
25
32
50
63
63
80
100
125
140
180
225
250
315
400
500
500
630
630
700
800
1000
1000
1000
1250
1250
-502-
Optional peripheral accessories
Contactor rated current (A)
10
10
16
16
25
32
50
63
80
95
120
135
170
230
280
315
380
450
580
580
630
700
780
900
960
1035
1222
1290