Goodrive350-19 Series VFD for Crane
Function
Name
code
Heavy-load
P91.14
speed-limit
detection frequency
Heavy-load
P91.15
speed-limit
detection delay
Electromotive
power upper limit of
P91.16
constant-power
speed boost/limit
Electricity
generation power
P91.17
upper limit of
constant-power
speed boost/limit
Description
Note: Light load speed boost mode 1 is
applicable to the open-loop mode.
Output
frequency
Set frequency
or speed limit
frequency
P91.14
P91.15
When the set frequency is greater than the
heavy load speed-limit detection frequency
(P91.14),
the
motor
becomes stable after reaching the detection
frequency (P91.14), and load detection is
performed after the time specified by P91.15.
The load detection value is used for heavy load
speed limit calculation. The load detection
value P94.01 can be viewed through the
keypad.
Setting range of P91.14: 0.00Hz–P02.02
Setting range of P91.15: 0.00–5.00s
Setting range of P94.01: 0.0% –150.0% (of the
motor rated torque)
Limited frequency f
Max. output
P00.03
f
lim
P91.14
T1
Constant power speed limit frequency = Power
upper limit * Motor rated frequency/Load
detection value
The constant power mode is used for speed
adjustment. The constant power speed limit
frequency under the present load is calculated
-315-
running
frequency
frequency
Limited frequency
corresponding to the load
Load
Tmax
Tn
Function parameters
Default Modify
○
40.00Hz
Time
○
0.35s
○
90.0%
T
○
100.0%