Goodrive350-19 Series VFD for Crane
Function
Name
code
Light/heavy load
P91.08
speed regulation
selection
Light-load
speed-boost target
P91.09
frequency setting
Light-load
P91.10
speed-boost
detection frequency
Light-load
speed-boost
P91.11
current detection
time
FWD light-load
P91.12
speed-boost
current detection
Description
VFD
running
status
Enabling zero
position
detection
S terminal
zero position
input signal
Zero
position
detection
P91.07
Analog AI2
1.00V
0
Normal
VFD fault
status
Setting range: 0.000–10.000s
0–5
0: Disable
1: Constant power speed boost
2: Constant power speed limit
3: Stepped speed limit
4: Light load speed boost 1 (by set current and
frequency)
5: Speed boost through external terminal signal
P91.08=4: Light load speed boost mode 1
(according to set current and frequency)
Output
frequency
P91.09
P00.10
Motor rated frequency
P91.10
Output
current
P91.12 or
P91.13
Light load speed boost after current verification
-313-
Stop
Enable
With zero position signal input
Zero position is valid
AdE fault
Light load speed boost after
current verification success
P91.11
Light load speed boost after
current verification success
Function parameters
Default Modify
0
70.00Hz
90.0%
Time
1.000s
Time
60.0%
◎
○
○
○
○