Goodrive350-19 Series VFD for Crane
drives lifting motor 2. After completing the lifting job, VFD 2 needs to drive the cross travel mechanism
motor independently.
To do this, VFD 2 needs to:
(1) Disable the master/slave mode and run independently.
(2) Switch the motor from lifting motor 2 to the cross travel mechanism motor.
(3) Switch motor and VFD parameters.
Braking resistor
(+)
R
R
S
S
VFD 1
T
T
Note: The power supply switchover of lifting motor 2 and the cross travel mechanism motor
must be controlled by the PLC.
Commissioning procedure:
1.
Set P90.00=6 (User-defined macro 1) for VFD 2, set running parameters for lifting motor 2
according to the following table of user-defined application macro parameter settings, and note
that A81.24=2 (Slave mode).
2.
Set P90.01=7 (User-defined macro 2) for VFD 2, set the parameters for cross travel mechanism
motor according to the following table of user-defined application macro parameter settings, and
note that A81.24=0 (Disable master/slave mode).
3.
When the S1 terminal of VFD 2 is invalid, VFD 2 drives lifting motor 2 and VFD 1 drives lifting
motor 1 to complete the lifting work. When the S2 terminal of VFD 2 is valid, VFD 2 independently
drives the cross travel mechanism motor to work.
Motor run
VFD 1
status
For a master,
Lifting run
P28.00=1
Cross
When no
travel
master/slave
Lifting motor 1
PB
U
M
V
3~
W
PE
CANH
CANL
CAN
Communication
card
VFD 2
For a slave,
A81.24=2
(P28.00=2)
When no
master/slave is
Braking resistor
Lifting motor 2
KM1
M
3~
W
PE
KM2
M
3~
Trolley motor
Communication
VFD 2
KM1 KM2
Terminal
S1
Clos
Open
Invalid
ed
ed
Open
Clos
Valid
ed
ed
-118-
Commissioning guidelines
(+)
PB
R
U
S
V
VFD 2
T
S1
COM
PW
CANH
+24V
CANL
CAN
card
Lifting
Lifting
motor
motor
1
2
Run
Run
Stop
Stop
R
S
T
Switch from
motor 1 to
motor 2
Cross
travel
mechanis
m motor
Stop
During
running,