Goodrive350-19 Series VFD for Crane
Function
Name
code
FWD/REV running
P01.14
switching mode
P01.15
Stop speed
Stop speed
P01.16
detection mode
Stop speed
P01.17
detection time
Terminal-based
running command
P01.18
protection at
power-on
Description
Output frequency f
Forward
Starting
frequency
Setting range: 0.0–3600.0s
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop
speed with a delay
0.00–100.00Hz
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
0.00–100.00s
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is
considered as valid during power-on, the VFD
is started automatically after the initialization.
2: The terminal running command is invalid at
power-on, and a fault is reported.
(Power-on terminal command exception POE).
During power on, the VFD does not run but
reports the fault, although the running
command terminal is valid. The fault disappears
only when the running command is canceled.
-155-
Switch over after
starting frequency
Switch over after
zero frequency
Time t
Deadzone
Reverse
time
Function parameters
Default Modify
◎
1
◎
0.20Hz
◎
0
◎
0.50s
○
0
Need help?