Goodrive350-19 Series VFD for Crane
Function
Name
code
Frequency
increment integral
P08.45
rate of the UP
terminal
Frequency integral
P08.46
rate of the DOWN
terminal
Action selection at
P08.47
power-off during
frequency setting
Initial electricity
P08.48
consumption high
Initial electricity
P08.49
consumption low bit
Magnetic flux
P08.50
braking
1: Valid for all frequency setting methods
2: Invalid for multi-step speed running when
multi-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0.01–50.00Hz/s
0.01–50.00Hz/s
0x000–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through DP
communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
Used to set the initial electricity consumption.
Initial electricity consumption = P08.48 × 1000
bit
+ P08.49
Setting range of P08.48: 0–59999kWh (k)
Setting range of P08.49: 0.0–999.9kWh
Used to enable magnetic flux braking.
0: Invalid
100–150: A greater coefficient indicates greater
braking strength.
Description
-206-
Function parameters
Default Modify
○
0.50Hz/s
○
0.50Hz/s
○
0x000
○
0kWh
○
0.0kWh
○
0