Goodrive350-19 Series VFD for Crane
1. Connect the PTC according to Figure 5-23 Wiring between PTC and analog terminals.
2. Set P92.22=4 to set the temperature sensor type to PTC.
3. Set P06.23 (often using the default value).
4. Set P06.24 and P06.25 according to the selected PTC model resistance and temperature curve.
5.
Check whether the actual PTC resistance is correct.
Function
Name
code
Type of sensor for
P92.22
AI to detect motor
temperature
AO1 output current
P06.23
setting
PTC resistance
P06.24
alarm threshold
PTC resistance
P06.25
alarm recovery
threshold
Actual PTC
P06.26
resistance
Description
4: PTC (supporting only AI1)
0.000–20.000mA
0–60000Ω
When P06.26 is greater than P06.24, the VFD
reports the alarm A-Aot and the system runs
normally.
0–60000Ω
When P06.26 is less than P06.25, the alarm A-Aot is
cleared.
0–60000Ω
-135-
Commissioning guidelines
Setting
4
4.000mA
750Ω
150Ω
0Ω