Goodrive350-19 Series VFD for Crane
Function
Name
code
Transmission error
P14.05
processing
Modbus
communication
P14.06
processing action
selection
User-defined
P14.07
running command
address
User-defined
P14.08
frequency setting
address
Modbus TCP
P14.09
communication
timeout time
P14.10
Enabling 485
Description
communication fault" (CE) if the communication
interval exceeds the value.
In general, the function code is set to 0.0. When
continuous communication is required, you can
set the function code to monitor communication
status.
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop in enabled stop mode without reporting
an alarm (applicable only to communication
mode)
3: Stop in enabled stop mode without reporting
an alarm (applicable to any mode)
0x000–0x111
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Communication password protection is
invalid.
1: Communication password protection is valid.
Hundreds place:
0: User-defined addresses specified by P14.07
and P14.08 are invalid.
1: User-defined addresses specified by P14.07
and P14.08 are valid.
0x0000–0xFFFF
Note:
This
parameter
user-defined
Modbus
address.
0x0000–0xFFFF
Note:
This
parameter
user-defined Modbus
address.
0.0–60.0s
Note: It is invalid when the value is 0.0.
0–1
-233-
specifies
the
run
command
specifies
the
frequency setting
Function parameters
Default Modify
0
0x000
0x2000
0x2001
5.0s
0