Goodrive350-19 Series VFD for Crane
Function
Name
code
P92.38
Enabling overload
Weighing
P92.39
calibration
P92.40
Peeled loading
P92.41 Non-empty loading
P92.42
Peeled torque
P92.43
Loaded torque
Description
stalling occurs, and then it reports the fault and
stops running.
Output frequency
Set frequency
0.5Hz
P92.37
Output current
P92.36
Fault state
0–2
0: Disable
1: Torque overload, determined by P92.04 and
P92.05.
2:
Weight
overload,
P92.39–P92.46.
Setting range of P92.39: 0–2
0: Normal
1: Peeled autotuning
2: Loaded autotuning
This parameter is automatically cleared after
autotuning is completed.
Setting range of P92.40: 0.0–20.00t
Setting range of P92.41: 0.0–20.00t
Setting range of P92.42: 0–250.0% (of the
motor rated torque)
Setting range of P92.43: 0–250.0% (of the
motor rated torque)
For peeled autotuning, when P92.39=1, the
LED keypad displays "LoAd1". After pressing
"Run", the autotuning starts, and the obtained
torque value is automatically saved to P92.42.
In addition, the VFD decelerates to stop. When
the VFD stops, the LED keypad does not
display "LoAd1".
For loaded autotuning, when you have entered
-332-
E-ds
determined
by
Function parameters
Default Modify
○
0
◎
0
○
0.00t
○
0.00t
○
0.0%
○
0.0%