Goodrive350-19 Series VFD for Crane
Function
Name
code
temperature
(2) Through an AI terminal
Figure 5-21 Wiring between analog terminals and PT100/PT1000
Note: Turn SW2 on the control board to "I" for current output.
Procedure
1.
Connect PT100/PT1000 according to Figure 5-21 Wiring between analog terminals and
PT100/PT1000.
2.
Set P92.22=1 to select PT100, or set P92.22=2 to select PT1000.
3.
Set P92.23 (AI detected motor OH protection threshold) and P92.24 (AI detected motor OH
pre-alarm threshold).
4.
Check whether P94.20 (AI detected motor temperature) is correct.
Function parameter settings
Function
Name
code
Type of sensor for
P92.22
AI to detect motor
temperature
AI detected motor
P92.23
overtemperature
protection threshold
AI detected motor
P92.24
overtemperature
Description
2: PT100 upper limit digital calibration autotuning
3: PT1000 lower limit digital calibration autotuning
4: PT1000 upper limit digital calibration autotuning
After autotuning is completed, the function code is
automatically cleared, and the calibration value is
automatically saved to the I/O card.
AO1
AI1
GND
VFD
Description
1: PT100
2: PT1000
0.0–200.0° C
When P94.20 is greater than P92.24, the motor
overtemperature (OT) fault is reported and the VFD
stops.
0.0–200.0° C
When P94.20 is greater than P92.24, the A-Aot
-132-
Commissioning guidelines
PT100
PT1000
Setting
Setting
1 or 2
110.0° C
90.0° C