Goodrive350-19 Series VFD for Crane
Function
Name
code
Restart after power
P01.21
Wait time for restart
P01.22
after power-off
P01.23
Start delay
P01.24
Stop speed delay 0.0–600.0s
Open-loop 0Hz
P01.25
output selection
DEC time for
P01.26
emergency stop
Time of starting
P01.27
segment of DEC S
curve
Time of ending
P01.28
segment of DEC S
curve
Short-circuit braking
P01.29
current
P01.19 ones place= 2)
The function code indicates whether the VFD
automatically runs after re-power on.
0: Disable
off
1: Enable. If the restart condition is met, the
VFD will run automatically after waiting the time
defined by P01.22.
The function code indicates the wait time before
the automatic running of the VFD that is
re-powered on.
Output frequency
Running
Setting range: 0.0–3600.0s (valid only when
P01.21 = 1)
After a VFD running command is given, the
VFD restarts running output with the delay
defined by P01.23 from the standby state, to
implement brake release.
Setting range: 0.0–600.0s
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0.0–60.0s
0.0–50.0s
0.0–50.0s
When the VFD starts in direct start mode
(P01.00 = 0), set P01.30 to a non-zero value
Description
t1=P01.22
t2=P01.23
t1
t2
Running
Power off
Power on
-157-
Function parameters
Default Modify
0
1.0s
t
0.0s
0.0s
0
2.0s
0.1s
0.1s
0.0%