Configuring networks
5.5 Configuring PROFINET IO with IRT
Ti/To values:
● "PROFIBUS Integrated_1 > Equidistance > Ti/To values of the PROFIBUS"
● "I/O device > PROFINET interface [x1] > Extended options > Isochronous mode"
Match the values and compile the project again.
5.5.12
Assigning drive addresses to the NCU machine data
Procedure
To enter configured addresses in the machine data in the TIA Portal, proceed as follows:
1. Check in the TIA Portal which addresses you have assigned to the drives (see Configuring
IO modules or drive telegrams (Page 106)).
2. Transfer the addresses to the machine data (e.g. via SINUMERIK Operate).
See Adapting I/O start addresses (Page 133).
Further information
● General information concerning this machine data is available in Chapter A4 of the
SINUMERIK 840D sl Supplementary Functions Manual: Digital and analog NCK I/Os for
SINUMERIK 840D sl.
● Specific information on the individual machine data can be found in the online help of
SINUMERIK Operate.
112
SINUMERIK STEP 7 Toolbox V15.1
Configuration Manual, 12/2018, A5E46279635B AA