Setting functions
8.3 Setpoints
8.3.5
Fixed speed as setpoint source
In many applications after switching on the motor, all that is needed is to run the motor at a
constant speed or to switch between different speeds.
Example: After it has been switched on, a conveyor belt only runs with two different
velocities.
Interconnecting the fixed speeds with a main setpoint
Figure 8-11
Table 8- 6
Parameter
p1070 = 1024
p1075 = 1024
Select direct or binary fixed setpoint
The converter distinguishes between two methods for selecting the fixed setpoints:
1. Direct selection:
You set 4 different fixed setpoints. By adding one or more of the four fixed setpoints, up
to 16 different resulting setpoints are obtained.
Figure 8-12
118
Fixed speeds as setpoint source
Setting the fixed speed as a setpoint source
Remark
Main setpoint
Interconnecting the main setpoint with fixed speeds.
Additional setpoint
Interconnecting the additional setpoint with fixed speeds
Simplified function diagram for directly selecting fixed setpoints
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA