Internal Ground-Fault Monitoring When Using A Current Measuring Module Or A 1St Generation Current / Voltage Measuring Module - Siemens SIMOCODE pro Operating Manual

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Parameters
4.3 Monitoring functions
4.3.1.4
Internal ground-fault monitoring when using a current measuring module or a 1st
generation current / voltage measuring module
Response
Here you can set how SIMOCODE pro will respond to an internal ground fault:
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Figure 4-30
Table 4- 30
Response
disabled
signaling
warn
tripping
delay
You can activate internal ground-fault monitoring by parameterization. It covers two different
operating conditions:
● Normal operation up to 2 x I
current setting I
● Start-up or overload operation to 2 x I
current setting I
detected.
Trip level activity, warning level
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
130
"Ground-fault Monitoring" function block
"Internal ground-fault monitoring" response
Internal ground fault
X (d)
X
X
X
0 to 25.5 s (default: 0.5 s)
. The actual operating current must be smaller than twice the
s
. Residual currents of > 30 % of the current setting I
s
. Residual currents of > 15 % of the effective motor current will be
s
. The actual operating current is greater than 2x the
s
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
are detected.
s
SIMOCODE pro - Parameterize