6.3
Specifications
6.3.1
Input current operation
Note
The Power Module is only for operation at a maximum line impedance of 1% Vk. No line
reactor can be used with the Power Module.
NOTICE
UL-certified fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit breakers or self-
protected combination motor controllers must be used.
Power Module specifications
Table 6- 2
PM230 Frame Sizes A, 3 AC 380 V ... 480 V, ± 10%
Order No.
Class A filter
Class B filter
Values based on Low Overload
● LO power
● LO input current
● LO Output current
Values based on High Overload
● HO power
● HO input current
● HO output current
Common values
● Power losses
● Fuse
● Required cooling air flow
● Cross section of line and
motor cable
● Tightening torque for line and
motor cable
● Weight
Power Module PM230 IP55
Hardware Installation Manual, 2010-07-02, A5E02923635A AB
6SL3223-0DE13-7AA0
6SL3223-0DE13-7BA0
0.37 kW
1.3 A
1.3 A
0.25 kW
0.9 A
0.9 A
0.06 kW
10 A
7 l/s
1 ... 2.5 mm
2
0.5 Nm
4.3 kg
6SL3223-0DE15-5AA0
6SL3223-0DE15-5BA0
0.55 kW
1.8 A
1.7 A
0.37 kW
1.3 A
1.3 A
0.06 kW
10 A
7 l/s
1 ... 2.5 mm
2
0.5 Nm
4.3 kg
Technical specifications
6.3 Specifications
6SL3223-0DE17-5AA0
6SL3223-0DE17-5BA0
0.75 kW
2.3 A
2.2 A
0.55 kW
1.8 A
1.7 A
0.06 kW
10 A
7 l/s
1 ... 2.5 mm
2
0.5 Nm
4.3 kg
75