B.2
Representation of analog values in the current measuring ranges
The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
* For measuring type "2-wire transducer", negative values are not possible for the range "0 to 20 mA".
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD00-0BA1)
Manual, 07/2014, A5E03551866-AC
B.2 Representation of analog values in the current measuring ranges
Current measuring range ±20 mA
Current measuring range
Hex.
±20 mA
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
<-23.52 mA
Current measuring ranges 0 to 20 mA and 4 to 20 mA
Current measuring range
Hex.
0 to 20 mA *
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
ED00
-3.52 mA
8000
<-3.52 mA
Therefore, no underrange or underflow exists here.
Representation of analog values
4 to 20 mA
>22.81 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
<1.185 mA
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
33