Configuration Data Of The Standard Mappings - Siemens SIPROTEC Manual

Bay control unit, communication module, profibus dp bus mapping
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

2.4

Configuration data of the standard mappings

Standard mapping
3-1
Standard mapping
3-2
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
There are three standard mappings (standard mapping 3-1 to standard mapping 3-4)
available for the SIPROTEC device 6MD662/3/4 which differ in the available data size
of the PROFIBUS DP messages.
If the 6MD663 or 6MD664 is used with a redundant PROFIBUS DP interface (ref. to
chap. 1) then standard mapping 3-3 or 3-4 has to be selected.
The standard mapping 3-1 contains:
Output direction:
• Handshake byte for event list via PROFIBUS DP
• 11 Double commands
• 37 Single commands
Input direction:
• 11 Double-point indications
• 58 Single-point indications
• 10 Measured values (integer)
• 4 Metered measurands (counters, unsigned long)
• Handshake byte and three message blocks for event list via PROFIBUS DP
The standard mapping 3-2 contains:
Output direction:
• 14 Double commands
• 24 Single commands
• 2 Transformer tap change commands
Input direction:
• 14 Double-point indications
• 84 Single-point indications
• 13 Measured values (integer)
• 4 Metered measurands (counters, unsigned long)
• 2 Transformer tap position indications
Data of the PROFIBUS DP messages
47