Configuration Data Of The Standard Mappings 2-1 To 2-4 - Siemens SIPROTEC4 7SJ61 Protocol Manual

Communication module profibus-dp bus mapping
Hide thumbs Also See for SIPROTEC4 7SJ61:
Table of Contents

Advertisement

Data in the PROFIBUS-DP messages
1.4

Configuration data of the standard mappings 2-1 to 2-4

Standard
mapping 2-1
Standard
mapping 2-2
Standard
mapping 2-3
1-6
There are three standard mappings (standard mapping 2-1 to standard
mapping 2-4) available for the SIPROTEC devices 7SJ61...7SJ63,
7SJ65, 6MD63 for parameterization with DIGSI version 4.2 or higher
which differ in the data size of the PROFIBUS-DP messages.
The standard mapping 2-1 contains:
Output direction:
7 double-point commands
29 single-point commands
Input direction:
7 double-point indications
146 single-point indications,
25 measured values (integer)
6 metered measureands (unsigned long)
Fault locator: Fault location (integer)
Counter of operating hours (unsigned long)
The standard mapping 2-2 contains:
Output direction:
7 double-point commands
29 single-point commands
Input direction:
7 double-point indications
114 single-point indications
10 measured values (integer)
2 metered measurands (unsigned long)
Counter of operating hours (unsigned long)
The standard mapping 2-3 contains:
Output direction:
8 double-point commands
24 single-point commands
Input direction:
8 double-point indications
64 single-point indications
21 measured values (integer)
6 metered measurands (unsigned long)
Counter of operating hours (unsigned long)
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping