F31123 (N, A)

Encoder 1: Signal level A/B unipolar outside tolerance

Message value:
Fault cause: %1 bin
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The unipolar level (AP/AN or BP/BN) for encoder 1 is outside the permissible tolerance.
Fault value (r0949, interpret binary):
Bit 0 = 1: Either AP or AN outside the tolerance.
Bit 16 = 1: Either BP or BN outside the tolerance.
The unipolar nominal signal level of the encoder must lie in the range 2500 mV +/- 500 mV.
The response thresholds are < 1700 mV and > 3300 mV.
Note:
The signal level is not evaluated unless the following conditions are satisfied:
- Sensor Module properties available (r0459.31 = 1).
- Monitoring active (p0437.31 = 1).
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- make sure that the encoder cables and shielding are installed in an EMC-compliant manner.
- check the plug connections and contacts of the encoder cable.
- check the short-circuit of a signal cable with mass or the operating voltage.
- replace the encoder cable.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31125 (N, A)

Encoder 1: Amplitude error track A or B overcontrolled

Message value:
A track: %1, B-track: %2
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The amplitude of track A or B for encoder 1 exceeds the permissible tolerance band.
Fault value (r0949, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Signal level, track B (16 bits with sign).
xxxx = Signal level, track A (16 bits with sign).
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response threshold is > 750 mV. This fault also occurs if the A/D converter is overcontrolled.
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
Note for Sensor Modules for resolvers (e.g. SMC10):
The nominal signal level is at 2900 mV (2.0 Vrms). The response threshold is > 3582 mV.
A signal level of 2900 mV peak value corresponds to the numerical value 6666 hex = 26214 dec.
Note:
The analog values of the amplitude error are not measured at the same time with the hardware fault output by the
Sensor Module.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- check that the encoder cables and shielding are routed in compliance with EMC.
- replace the encoder or encoder cable.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms