Product overview

2.4 Reset communication module to factory settings

cables using proven 3-wire technology. IO-Link is backward compatible to conventional
sensors. The switching state and data channels are designed with trusted 24 V DC
technology.
Reference
Additional information can be found in the IO-Link System
(https://support.automation.siemens.com/WW/view/en/65949252) function manual.
2.3
Replacing the IO-Link Master CM 8xIO-Link communication
module
Master Backup
You can back up the parameters of your module with the function block "LIOLink_Master".
The "LIOLink_Master" function block is used to read all relevant IO-Link device and IO-Link
Master parameters. The parameters can be stored retentively at a central location, such as in
a data block in the IO controller.
The status of the IO-Link devices or IO-Link ports stored in the IO-Link Master can be restored
with the "LIOLink_Master" function block.
As a result, the IO-Link ports and the IO-Link Master are configured with the values stored in
the master backup.
A typical application is the restoration of parameters after replacement of the IO-Link Master.
Module
as of V 1.0
Compatibility table of the firmware versions
NOTE
Availability
Note that the Master Backup function is available only for IO-Link devices that are specified
for the IO-Link Standard as of V1.1.
You can find additional information on the master backup functions in the section
'Integration into the automation system' in the IO-Link System
(https://support.industry.siemens.com/cs/ww/en/view/65949252) function manual.
2.4
Reset communication module to factory settings
Effects of resetting to the factory settings
Use the "Reset to factory settings" function to restore the parameter assignments of your IO-
Link Master CM 8xIO‑Link communication module made with S7-PCT to the factory state.
14
Firmware version
Function block LIOLink_Master
as of V 1.0.0
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
Equipment Manual, 08/2022, A5E45488510-AB