Electronic Air-Fuel Ratio Control; General; Behavior Outside Operation; Running Speed - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

78/213
Building Technologies
HVAC Products
9

Electronic air-fuel ratio control

9.1 General

Electronic air-fuel ratio control is used for controlling the burner's actuators depending
on burner output. It is possible to connect 2 actuators and, optionally, one VSD.
Resolution is 0.1° with the actuators and 0.1% with the VSD. Output can be regulated in
increments of 0.1% in modulating mode and with a maximum of 3-stages in multistage
mode.
To reduce the amount of electric power required for the actuators, they are never oper-
ated simultaneously, but in successive order, or alternately.

9.2 Behavior outside operation

Outside the running position, the actuators approach the different positions in succes-
sive order.
The program phase determines the position to be approached.

9.2.1 Running speed

The actuators' running speed is fixed at 5 seconds for a positioning angle of 90°.
The ramp speed of the VSD can be adjusted separately for higher and lower speeds.
No.
Parameter
522
Ramp up
523
Ramp down
The setting also applies to the running position (refer to subsection Running position ).
9.2.2 No-load position
This position is approached in the Home run (10), Standby (12) and Lockout position
(00) phases.
The position can be set via the following parameters:
Parameter
501.00
502.00
503.00
Basic documentation LMV37.4...
9 Electronic air-fuel ratio control
Actuator
No-load position fuel actuator
No-load position air actuator
No-load speed VSD
CC1P7546en
01.12.2009