4.4 Address space

4.4
Address space
Address space of the technology module
Table 4- 3
Range
You define the contents of the address space in the TM FAST application (Page 41).
4.5

Reaction to CPU STOP

You set the response of the technology module to CPU STOP in the device configuration with
the basic parameters (Page 22).
Table 4- 4
Disable all outputs
Take over from TM FAST
application
In addition, the signal CPU_STOP is available to the TM FAST application so that a STOP of the
CPU is detected and a suitable response of the TM FAST application can be programmed in
the logic. You can find additional information about the signals in the system logic in the
programming manual Creating a TM FAST Application
(https://support.industry.siemens.com/cs/ww/en/view/109816088).
28
Range of the input addresses and output addresses of the TM FAST
Inputs
32 bytes
Reaction of technology module to CPU STOP
Reaction of technology module
The technology module switches off all outputs up to the next STOP-RUN
transition. After a STOP-RUN transition, the TM FAST application retakes
control over the outputs.
The technology module continues to operate. The outputs continue to
switch according to the TM FAST application.
Outputs
32 bytes
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA