4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged once the permissible temperature limit minus 5 K has been fallen below.
F30037
Power unit: Rectifier overtemperature
Message value:
%1
Message class:
Power electronics faulted (5)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature in the rectifier of the power unit has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- line supply phase failure.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- check the line supply phases.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05004 has been undershot.
A30038
Power unit: Capacitor fan monitoring
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
The capacitor fan signals a fault.
Remedy:
Replace the capacitor fan in the power unit.
F30039
Power unit: Failure capacitor fan
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF
Component:
Power Module
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
The capacitor fan has failed.
Remedy:
Replace the capacitor fan in the power unit.
1662
Propagation:
LOCAL
Propagation:
GLOBAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150