4 Faults and alarms
4.2 List of faults and alarms
F30105
PU: Actual value sensing fault
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
B_INF, VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one incorrect actual value channel was detected on the Power Stack Adapter (PSA).
The incorrect actual value channels are displayed in the following diagnostic parameters.
Remedy:
Evaluate the diagnostic parameters.
If the actual value channel is incorrect, check the components and if required, replace.
F30314
Power unit: 24 V power supply overloaded by PM
Message value:
-
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply through the Power Module (PM) is overloaded.
An external 24 V power supply via X124 on the Control Unit is not connected.
Remedy:
Connect an external 24 V power supply via X124 at the Control Unit.
A30315 (F)
Power unit: 24 V power supply overloaded by PM
Message value:
-
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply through the Power Module (PM) is overloaded.
An external 24 V power supply via X124 on the Control Unit is not connected.
Remedy:
Connect an external 24 V power supply via X124 at the Control Unit.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A30502
Power unit: DC link overvoltage
Message value:
%1
Message class:
DC link overvoltage (4)
Drive object:
VECTOR_G
Component:
Power Module
Reaction:
NONE
Acknowledge:
NONE
Cause:
The power unit has detected overvoltage in the DC link on a pulse inhibit.
- device connection voltage too high.
- line reactor incorrectly dimensioned.
Alarm value (r0949, interpret decimal):
DC link voltage [1 bit = 100 mV].
See also: r0070 (Actual DC link voltage)
Remedy:
- check the device supply voltage (p0210).
- check the dimensioning of the line reactor.
See also: p0210 (Drive unit line supply voltage)
1674
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL