Digital Input/Output Bytes And System Variables - Siemens SINUMERIK 840Di sl Commissioning Manual

Hide thumbs Also See for SINUMERIK 840Di sl:
Table of Contents

Advertisement

11.7.4

Digital input/output bytes and system variables

Digital inputs
The following configuration example shows the relationship between digital input bytes and
system variables by means of the configuration of 3 digital inputs bytes.
This configuration example requires the following:
● MCI board extension module: 1 input byte
● PROFIBUS DP signal modules: 2 input bytes
The MCI board extension module is always assigned to a digital input byte. Digital input
bytes of external signal modules must therefore always be counted as additional input bytes:
● MD10350 $MN_FASTIO_DIG_NUM_INPUTS = 1 + m,
Because the 1st input byte is permanently assigned to the MCI board extension module, only
the input bytes of the external signal modules have to be explicitly assigned to the system
variables.
● MD10366 $MN_HW_ASSIGN_DIG_FASTIN[0] -> 1. external input byte
● MD10366 $MN_HW_ASSIGN_DIG_FASTIN[1] -> 2. external input byte
Figure 11-31 Configuration example: 3 digital input bytes
If the optional MCI board extension module does not exist, assignment in the machine data
must still be made as stated because the 1st input byte is internally permanently assigned to
this module. System variables $A_IN[1] to $A_IN[4] do not then contain information.
Digital outputs
Digital outputs must be configured as described above for digital inputs.
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
with m = number of input bytes of external signal modules
NC Commissioning with HMI Advanced
11.7 Digital and analog I/O devices
471

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 840die sl control

Table of Contents