Siemens SINAMICS S110 List Manual page 831

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

<1>
Standstill threshold
n_act smooth
p1225
r0063
(r0063)0
[4710.6]
n_stop n_thresh
0.0...210 000.0 [rpm]
p1226 (20.0)
n_set before filt.
r0060
[5020.4]
p1275.02 (0)
Brk close standstill
0
p1224[0]
(0)
1
1
p1224[1]
(0)
<3>
p1224[2]
(0)
p1224[3]
(0)
OFF1 present
<4>
OFF3 present
<1> Shutdown threshold of the standstill detection. In this case (e.g. when using a brake), another criterion than the
speed actual value can be selected to clear the pulses. Otherwise, we recommend to keep the factory setting.
<2> For p1276 = 300.000 s, the timer is deactivated, i.e. the timer output is always 0. Note: When operating a
motor with a brake which must not be applied while the motor is rotating, the monitoring time of both timers
must be set to 300 s.
<3> For operation without brake, p1224[0...3] must be 0 (factory setting) in order to avoid undesirable interaction
with the sequence control.
<4> The internal signal comprises signals that lead to OFF1 or OFF3, e.g. BICO or fault response.
1
2
DO: SERVO
Braking control - Extended braking control, zero-speed detection (r0108.14 = 1)
Brake, threshold value
0.000...10.000 [s]
fallen below
p1228 (0.000)
r1229.7
1
T
0
0
Brake,
<2>
monitoring
0.000...300.000 [s]
time expired
p1227 (4.000)
r1229.8
1
T
0
0
p1275.03 (0)
<2>
0.000...300.000 [s]
p1276 (300.000)
0
T
0
-1
1
3
4
Close brake from standstill detection
SET
&
Q
(Q=1)
RESET
Q
(Q=0)
1
5
6
Function diagram
fp_2704_98_eng.vsd
SINAMICS S110
30.09.11 V04.04.00
Background
Refer to [1020.7]
[2707.1]
[2711.1]
7
8
- 2704 -