Parameter
List of parameters
3:
4:
5:
6:
7:
8:
9:
9999: Do not calculate
p20255
PT1 1 run sequence / PT1 1 RunSeq
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: Unsigned16
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
0
Description:
Setting parameter for the run sequence of instance PT1 1 within the run-time group set in p20254.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20256[0...1]
CI: INT 0 inputs / INT 0 inputs
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: Unsigned32 / FloatingPoint32
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
-
Description:
Sets the signal source of input quantity X and of setting value SV of instance INT 0 of the integrator.
Index:
[0] = Input X
[1] = Setting value SV
p20257
INT 0 upper limit value LU / INT 0 upper lim LU
CU_S110-CAN,
Can be changed: T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN,
P-Group: -
SERVO_S110-CAN
Not for motor type: -
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Min
-340.28235E36
Description:
Sets the upper limit value LU of instance INT 0 of the integrator.
1-722
Run-time group 3
Run-time group 4
Run-time group 5
Run-time group 6
Run-time group 7
Run-time group 8
Run-time group 9
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
32000
Calculated: -
Dynamic index: -
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
340.28235E36
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 1
Func. diagram: 7262
Unit selection: -
Expert list: 1
Factory setting
680
Access level: 1
Func. diagram: 7264
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 7264
Unit selection: -
Expert list: 1
Factory setting
0.0000