Siemens SINAMICS S110 List Manual page 638

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
p10130
SI SDI positive input terminal (processor 2) / SI SDI pos DI P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the fail-safe digital input (F-DI) for the "SDI positive" function.
Value:
0:
1:
2:
3:
255:
Note:
If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
p10131
SI SDI negative input terminal (processor 2) / SI SDI neg DI P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the fail-safe digital input (F-DI) for the "SDI negative" function.
Value:
0:
1:
2:
3:
255:
Note:
If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
p10139
SI Safe State signal selection (processor 2) / SI Safe State Sel
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Unsigned32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the signals for the drive group specific signal "Safe State".
Bit 0 = Power_removed
Bit 1 = SS1_active
Bit 2 = SS2_active
Bit 3 = SOS_active
Bit 4 = SLS_active
1-638
Statically active
F-DI 0
F-DI 1
F-DI 2
Statically inact
Statically active
F-DI 0
F-DI 1
F-DI 2
Statically inact
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2856
Unit selection: -
Expert list: 1
Factory setting
0000 0001 bin

Hide quick links:

Advertisement

Table of Contents
loading