Faults and alarms
List of faults and alarms
Fault value (r0949, decimal interpretation):
Drive object with enabled closed-loop control.
Remedy:
Withdraw the pulse enable on all drives and re-activate the motor data identification.
F08510 (A)
COMM BOARD: Send configuration data invalid
Message value:
%1
Drive object:
CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
COMM BOARD did not accept the send-configuration data.
Fault value (r0949, decimal interpretation):
Return value of the send-configuration data check.
Remedy:
Check the send configuration data.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A08526 (F)
PROFINET: No cyclic connection
Message value:
-
Drive object:
CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no connection to a PROFINET controller.
Remedy:
Establish the cyclic connection and activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
A08565
CBE20: Consistency error affecting adjustable parameters
Message value:
-
Drive object:
CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8925 = 1) for the PROFINET interface.
The currently set configuration has not been activated.
Possible causes:
- IP address, subnet mask or default gateway is not correct
- IP address or station name used twice in the network
- station name contains invalid characters, etc.
See also: p8920 (PN Name of Station), p8921 (PN IP address of station), p8922 (PN Default Gateway of Station),
p8923 (PN Subnet Mask of Station)
Remedy:
Check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925 = 1).
See also: p8925 (PN interface configuration)
F08700 (A)
CAN: Communications error
Message value:
%1
Drive object:
All objects
Reaction:
OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A CAN communications error has occurred.
Fault value (r0949, decimal interpretation):
1: The error counter for the send telegrams has exceeded the BUS OFF value 255. The bus disables the CAN con-
troller.
- bus cable short circuit.
- incorrect baud rate.
- incorrect bit timing.
3-1122
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3