Siemens SINAMICS S110 List Manual page 978

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Faults and alarms
List of faults and alarms
F01010
Drive type unknown
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An unknown drive type was found.
Fault value (r0949, decimal interpretation):
Drive object number (refer to p0101, p0107).
Remedy:
- replace Power Module.
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F01011 (N)
Download interrupted
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The project download was interrupted.
Fault value (r0949, decimal interpretation):
1: The user prematurely interrupted the project download.
2: The communication cable was interrupted (e.g. cable breakage, cable withdrawn).
3: The project download was prematurely ended by the commissioning software (e.g. STARTER, SCOUT).
100: Different versions between the firmware version and project files "Download from card".
Note:
The response to an interrupted download is the state "first commissioning".
Remedy:
- check the communication cable.
- download the project again.
- boot from previously saved files (power-down/power-up or p0976).
- when downloading from the card, use the matching version.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F01012 (N)
Project conversion error
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
When converting the project of an older firmware version, an error occurred.
Fault value (r0949, decimal interpretation):
Parameter number of the parameter causing the error.
For fault value = 600, the following applies:
The temperature evaluation is no longer assigned to the power unit but to the encoder evaluation.
Notice:
Monitoring of the motor temperature is no longer ensured.
Remedy:
Check the parameter indicated in the fault value and correctly adjust it accordingly.
For fault value = 600:
Parameter p0600 must be set to the values 1, 2 or 3 in accordance with the assignment of the internal encoder eval-
uation to the encoder interface.
Value 1 means: The internal encoder evaluation is assigned to the encoder interface 1 via p0187.
Value 2 means: The internal encoder evaluation is assigned to the encoder interface 2 via p0188.
Value 3 means: The internal encoder evaluation is assigned to the encoder interface 3 via p0189.
- If necessary, the internal encoder evaluation must be assigned to an encoder interface via parameters p0187,
p0188 or p0189 accordingly.
- If necessary, upgrade the firmware to a later version.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
3-978
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents