A30640 (F)
SI MM: Fault in the shutdown path of the second channel
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Motor Module has detected a communication error with the higher-level control or the TM54F to transfer the
safety-relevant information or there is a communication error between motor modules connected in parallel.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, decimal interpretation):
Only for internal Siemens troubleshooting.
Remedy:
For the higher-level control, the following applies:
- check the PROFIsafe address in the higher-level control and Motor Modules and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (power off/on) for all components.
For TM54F, carry out the following steps:
- start the copy function for the node identifier (p9700 = 1D hex).
- acknowledge hardware CRC (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (power off/on) for all components.
For a parallel connection:
- check the PROFIsafe address in the Control Unit and Motor Module and if required, align.
- save all parameters (p0977 = 1).
- carry out a POWER ON (power off/on) for all components.
The following generally applies:
- upgrade the Motor Module software.
Note:
MM: Motor Module
SI: Safety Integrated
See also: p9810 (SI PROFIsafe address (processor 2))
Reaction upon F:
NONE (OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
F30649
SI MM: Internal software error
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal error in the Safety Integrated software on the Motor Module has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- re-commission the Safety Integrated function and carry out a POWER ON.
- upgrade the Motor Module software.
- contact the Hotline.
- replace the Motor Module.