Faults and alarms
List of faults and alarms
A01069
Parameter backup and device incompatible
Message value:
-
Drive object:
CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the device type do not match (e.g. a memory card with the parameter
backup of a SINAMICS DCM is inserted in SINAMICS G110).
The module boots with the factory settings.
Remedy:
- insert a memory card with compatible parameter backup and carry out a POWER ON.
- insert a memory card without parameter backup and carry out a POWER ON.
- remove the memory card and carry out POWER ON.
- save the parameters (p0977 = 1).
A01069
Parameter backup and device incompatible
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the device type do not match (e.g. a memory card with the parameter
backup of a SINAMICS S120 is inserted in SINAMICS G150).
The module boots with the factory settings.
Remedy:
- insert a memory card with compatible parameter backup and carry out a POWER ON.
- insert a memory card without parameter backup and carry out a POWER ON.
- save the parameters (p0977 = 1).
A01099
Tolerance window of time synchronization exited
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time master exited the selected tolerance window for time synchronization.
See also: p3109 (RTC real time synchronization, tolerance window)
Remedy:
Select the re-synchronization interval so that the synchronization deviation between the time master and drive sys-
tem lies within the tolerance window.
See also: r3108 (RTC last synchronization deviation)
F01105 (A)
CU: Insufficient memory
Message value:
%1
Drive object:
All objects
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets,
OA applications, blocks, etc).
Fault value (r0949, decimal interpretation):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, OA applications,
blocks, etc).
- use an additional Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
3-988