Parameter
List of parameters
Dependency:
Refer to: p9548
Refer to: C01706
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
p9349
SI Motion slip velocity tolerance (processor 2) / SI Mtn slip P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [mm/min]
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitor-
ing channels.
Dependency:
Refer to: p9301, p9342, p9549
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
If the "actual value synchronization" is not enabled (p9301.3 = 0), then the value parameterized in p9342 is used as
tolerance in the crosswise data comparison.
p9349
SI Motion slip velocity tolerance (processor 2) / SI Mtn slip P2
SERVO_S110-CAN
Can be changed: C2(95)
(Safety rot),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Safety Integrated
(Safety rot),
Not for motor type: -
SERVO_S110-PN
(Safety rot)
Min
0.00 [rpm]
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitor-
ing channels.
Dependency:
Refer to: p9301, p9342, p9549
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
If the "actual value synchronization" is not enabled (p9301.3 = 0), then the value parameterized in p9342 is used as
tolerance in the crosswise data comparison.
p9351
SI Motion SLS changeover delay time (processor 2) / SI Mtn SLS t P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the delay time for the SLS changeover or for the changeover from SLS to SOS for the function "Safely-Limited
Speed" (SLS).
When transitioning from a higher to a lower safely-limited velocity/speed stage or to the safe operating stop (SOS),
within this delay time, the "old" velocity stage remains active.
Even if SLS or SOS is activated from non safety-related operation, then this delay is still applied.
Dependency:
Refer to: p9551
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SLS: Safely-Limited Speed
SOS: Safe Operating Stop
1-540
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
6000.00 [mm/min]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
6000.00 [rpm]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
600000000.00 [µs]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.00 [mm/min]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.00 [rpm]
Access level: 3
Func. diagram: 2825
Unit selection: -
Expert list: 1
Factory setting
100000.00 [µs]