___________________ SINAMICS S110 Preface ___________________ Fundamental safety instructions ___________________ SINAMICS System overview ___________________ Mains connection and line- side power components S110 SINAMICS S110 ___________________ Blocksize Power Modules (PM240-2) ___________________ DC link components Manual ___________________ Power components on the motor side...
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
(mailto:docu.motioncontrol@siemens.com). My Documentation Manager At the following address (http://www.siemens.com/mdm), you can find information on how to create your own individual documentation based on Siemens' content, and adapt it for your own machine documentation. Training At the following address (http://www.siemens.com/sitrain), you can find information about SITRAIN (Siemens training on products, systems and solutions for automation and drives).
Page 6
Installation/assembly SINAMICS S110 Manual • Commissioning STARTER commissioning tool • SINAMICS S110 Getting Started • SINAMICS S110 Function Manual Drive Functions • SINAMICS S110 List Manual • Usage/operation SINAMICS S110 Function Manual Drive Functions • SINAMICS S110 List Manual •...
(https://support.industry.siemens.com/cs/ww/en/ps/13231/cert). You can obtain an up-to-date list of currently certified components on request from your local Siemens office. If you have any questions relating to certifications that have not yet been completed, please ask your Siemens contact person.
Page 8
Spare parts Spare parts are available on the Internet at the following address (https://support.industry.siemens.com/sc/ww/en/sc/2110). Ground symbols Table 2 Symbols Symbol Meaning Connection for protective conductor (PE) Ground (e.g. M 24 V) Connection for function potential bonding SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 9
DC link and the output (> 1 MΩ) so that the possible voltage as result of the voltage divider with the impedance of the ground connection between the motor and converter is less than 50 VAC or 120 VDC. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Residual risks of power drive systems ..................23 System overview ........................... 25 Field of application ........................25 Platform Concept and Totally Integrated Automation ............. 26 Overview of SINAMICS S110 ....................28 System data ..........................29 Derating ..........................31 Mains connection and line-side power components ................35 Introduction ..........................
Page 12
Motor reactors ........................119 6.1.1 Description ........................... 119 6.1.2 Safety instructions for motor reactors .................. 119 6.1.3 Dimension drawings ......................121 6.1.4 Mounting ..........................125 6.1.5 Electrical connection ......................126 6.1.6 Technical data ........................127 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 15
Safety instructions for service and maintenance ..............245 11.2 Service and maintenance for components, Blocksize format ..........246 11.2.1 Replacing hardware components ..................246 11.2.2 Replacing the fan on the PM240-2 ..................246 11.3 Forming the DC link capacitors ..................... 248 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 16
Table of contents 11.4 Spare parts ........................... 251 11.5 Recycling and disposal ......................251 Annex ..............................253 List of abbreviations ......................253 Documentation overview ...................... 262 Spring-type terminals/screw-type terminals ................. 263 Index ..............................265 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Touching live components can result in death or severe injury. • Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV- (Protective Extra Low Voltage) output voltages for all connections and terminals of the electronics modules. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 18
When opening plug connections in operation, arcs can result in severe injury or death. • Only open plug connections when the equipment is in a no-voltage state, unless it has been explicitly stated that they can be opened in operation. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 19
This can cause severe injury or even death. This can also result in increased downtime and reduced service lives for devices/systems. • Ensure compliance with the specified minimum clearance as ventilation clearance for the respective component. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 20
• Only put your plant into live operation once you have guaranteed that the functions relevant to safety are running correctly. Note Important safety notices for Safety Integrated functions If you want to use Safety Integrated functions, you must observe the safety notices in the Safety Integrated manuals. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
– Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring • Only place electronic components, modules or devices on conductive surfaces (table with ESD surface, conductive ESD foam, ESD packaging, ESD transport container). SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
Inverters of the Open Type/IP20 degree of protection must be installed in a metal control cabinet (or protected by another equivalent measure) such that contact with fire inside and outside the inverter is not possible. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 24
Assuming that conductive contamination at the installation site can definitely be excluded, a lower degree of cabinet protection may be permitted. For more information about residual risks of the components in a drive system, see the relevant sections in the technical user documentation. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
System overview Field of application SINAMICS is the family of drives from Siemens designed for machine and plant engineering applications. SINAMICS offers solutions for all drive tasks: ● Simple pump and fan applications in the process industry. ● Complex individual drives in centrifuges, presses, extruders, elevators, as well as conveyor and transport systems.
SINAMICS S110 supports PROFIBUS DP, the standard field bus of the TIA system. It provides a high-performance, system-wide communication network which links all automation components: HMI, controls, drives and I/O devices.
Page 27
System overview 2.2 Platform Concept and Totally Integrated Automation Figure 2-2 SINAMICS as part of the Siemens modular automation system SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
2.3 Overview of SINAMICS S110 Overview of SINAMICS S110 SINAMICS S110 is the "simple servo" in the range of SINAMICS AC Drives. As a modular drive system for single axes in "servo" control mode, it is primarily used for simple positioning tasks in a wide range of industrial applications.
1.1 … 447 kW: 65 kA in accordance with UL508C (up to 600 V) UL approval applies only in conjunction with the fuses prescribed by Siemens and not with other types or circuit breakers alone. EMC Directive Category C3 (option) acc.
Page 30
CE (Low Voltage, EMC, and Machinery Directives) Approvals cULus acc. to UL 61800-5-1 CSA only with external surge protection devices C-Tick SEMI F47 KCC only with internal or external line filters WEEE (Waste Electrical & Electronic Equipment) RoHS SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
2000 m. If the neutral point is not grounded, you must connect an isolating transformer upstream, the secondary side of which is then grounded at the neutral point. A reduction of the line voltage phase-phase is not necessary. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 32
You will find the rated pulse frequency in the Technical Data of the relevant Power Module. Figure 2-5 Reduction of the output current as a function of the quotient of the pulse frequency and rated pulse frequency SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 33
Short-time duty operating state permissible for less than 2% of the operating time Sporadic short-time duty operating state only permissible for less than 1 % of the operating time SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Available line filter variants: ● Integrated (to achieve EMC category C2 or C3) ● External (to achieve EMC category C1) Figure 3-1 Example of a line connection for Power Modules Blocksize with no integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
• In TT systems, besides suitable overcurrent protection equipment, also use residual current devices (RCD) and, as of an infeed power of 55 kW or in extensive installations, also use residual current monitors (RCM). SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 37
1PB21-4UL0 1PB21-8UL0 1PB21-8UL0 with integrated line filter 1PB21-4AL0 1PB21-8AL0 1PB21-8AL0 Fuses UL Class J AJT50 AJT50 AJT50 Rated current Short-circuit current rating SCCR Fuses 3NE1817-0 3NE1818-0 3NE1818-0 NH IEC 60947 Rated current SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 38
1PE21-4UL0 1PE21-8UL0 1PE21-8UL0 with integrated line filter 1PE21-1AL0 1PE21-4AL0 1PE21-8AL0 1PE21-8AL0 Fuses UL Class J AJT35 AJT35 AJT35 AJT35 Rated current Short-circuit current rating SCCR Fuses 3NE1814-0 3NE1815-0 3NE1803-0 3NE1803-0 NH IEC 60947 Rated current SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 39
AJT150 Rated current Short-circuit current rating SCCR Fuses 3NA3832 3NA3836 NH IEC 60947 Rated current Fuses 3NE1022-0 3NE1224-0 UL Class J/NH IEC 60947 Rated current Line protection Line protection and protection of the Power Module SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
If no residual current device is used, touch protection can be ensured by means of double insulation or by isolating the Power Module from the supply system through a transformer. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
(on the line side of the main disconnect switch). To comply with the requirements of CSA C22.2 No. 14-05, a type VZCA7 or VZCA8 surge arrester is absolutely mandatory. The Raycap company has suitable surge arresters. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
To limit the switching overvoltage, the contactor coil must be connected to an overvoltage limiter (e.g. freewheeling diode or varistor). When the digital output is used to control the line contactor, you must consider the make/break capacity. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Insufficient ventilation clearances result in overheating with danger to persons as a result of smoke and fire. Further, the line filter can be thermally damaged. • Ensure 100-mm ventilation clearances above and below the line filter. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Damage of further loads due to incorrect line filters Unsuitable line filters can cause line harmonics, which damage or destroy loads connected to the same line supply. • Only use line filters released by Siemens for SINAMICS. 3.7.3 Classification of EMC behavior...
Page 45
Drive systems which correspond to category C4 may only be installed in the second environment. Note Expert An expert is a person or organization with the necessary experience for installing and/or commissioning drive systems (Power Drive Systems - PDS), including the associated EMC aspects. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Power Modules of the Blocksize series are all available in variants with an integrated line filter. The Power Modules of Category C3 and can only be used in the second environment. Category C4 Unfiltered Power Modules meet Category C4 and can only be used in the second environment. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Mains connection and line-side power components 3.7 Line filter 3.7.5 Dimension drawings Blocksize line filter Figure 3-2 Dimension drawing of the line filter, Power Module PM240-2 frame size FSA, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 48
Mains connection and line-side power components 3.7 Line filter Figure 3-3 Dimension drawing of the line filter, Power Module PM240-2 frame size FSB, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 49
Mains connection and line-side power components 3.7 Line filter Figure 3-4 Dimension drawing of the line filter, Power Module PM240-2 frame size FSC, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Installation example: Power Module PM240-2 (frame size FSA) with screening kit and line filter Table 3- 10 Connecting the line filter for the PM240-2 on the mounting surface Frame size Fastening Tightening torque 4 x M4 bolts 2.5 Nm 4 x M5 bolts 3 Nm SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Insufficient ventilation clearances can result in overheating with danger to persons as a result of smoke and fire. Further, increased failures can occur and the service life of components shortened. • Ensure 100-mm ventilation clearances above and below the component. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 53
Damage to the system due to impermissible line reactors An impermissible line reactor may cause damage to the system and any further loads operated on the same power network. • Only use line reactors that Siemens has authorized for SINAMICS. NOTICE Line reactor damage due to interchanged connections Interchanging the input and output connections will damage the line reactor.
Dimension drawing of line reactors, PM240-2 frame size FSA, 1.5 … 4.0 kW, all dimensions in mm and (inch) Figure 3-8 Dimension drawing of line reactors, PM240-2, frame size FSB, 4.0 … 7.5 kW, all dimensions in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Connecting the line reactor for the PM240-2 on the mounting surface Frame size Fastening Tightening torque 4 x M5 screws 6 Nm 4 x M5 nuts 4 x M5 washers 4 x M6 screws 10 Nm 4 x M6 nuts 4 x M6 washers SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Electrical Connection Line/load connection ① Line reactor ② Power Module Figure 3-10 Power Module with line filter ① Line reactor ② Line filter ③ Power Module Figure 3-11 Power Module with line reactor and line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Unit rating of the Power 0.55 … 1.1 1.1 … 3.0 3.0 … 7.5 5.5 … 15 Module x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
● Power Modules without line filter are permitted to be operated on all TN systems. ● Power Modules with integrated or external line filter are permitted to be operated only on TN systems with a grounded neutral point. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 59
Figure 3-14 IT system ● Power Modules without a line filter can be operated in all IT systems. ● Power Modules with an integrated or external line filter can be operated only in IT systems. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 60
If the drive unit is operated without a motor reactor in an IT system, a ground fault on the motor side of the Power Modules can cause damage to the drive line-up or trip the overcurrent protective equipment. • Always operate the Power Modules in an IT system with motor reactors. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
● Direct operation of the power supply connection components on the supply system ● Operation of the line connection components via an autotransformer ● Operation of the line connection components via an isolating transformer Figure 3-15 Overview of line connection variants for SINAMICS S110 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 62
(secondary side) must be connected between the supply and the drive system to protect the motor insulation from continuous excessive stress. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Operation of the line connection components on the supply line The SINAMICS S110 drive system is designed to be directly connected to TN and TT systems with a grounded neutral point as well as to IT systems without a line filter with rated voltages from 3-phase 380 V to 480 V AC and 1-phase 200 V to 240 V AC.
An autotransformer can be used to adapt the voltage in the range up to 3-phase 480 VAC +10% or 240 VAC +10%. Application example: ● The motor insulation must be protected from excessive voltages. Figure 3-18 Auto-transformers SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
● The installation altitude is greater than 2000 m above sea level. ● A line filter should always be used for all systems that are not TN or TT systems with grounded neutral point. Figure 3-19 Isolating transformer SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 66
Mains connection and line-side power components 3.9 Line connection variants SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Table 4- 1 Overview of PM240-2 Power Modules (selection) Power Module frame size FSA, with and with- Push Through Power Module frame size FSA, with out an integrated line filter and without an integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 68
Power Module frame size FSC, with and with- Push Through Power Module frame size FSC, with out integrated line filter and without an integrated line filter Power Module frame size FSD with and with- out an integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 69
Blocksize Power Modules (PM240-2) 4.1 Description Power Module frame size FSE with and with- out an integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Danger to life due to hazardous voltage when an unsuitable power supply is connected Death or serious injury can result when live parts are touched in the event of a fault. • Only use the intended supply voltage to operate the Power Modules. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 71
- Front: 100 mm (3.94 inch) • Only install devices in this area that do not obstruct the flow of cooling air. • Ensure that the cooling air can flow through the Power Modules unobstructed. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 72
• In the case of plug-in power terminals, check that the interlock of the connectors on the converter housing is intact. Note Malfunctions on non-Siemens equipment caused by high-frequency faults in residential environments In the first environment, Category C2 according to EMC product standard IEC 61800-3 (residential, commercial and industrial sector), the device may cause high-frequency disturbance, which can result in malfunctions in other equipment.
Blocksize Power Modules (PM240-2) 4.3 Interface description Interface description 4.3.1 Overview Figure 4-1 PM240-2, frame size FSA (view from below and front) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 74
Blocksize Power Modules (PM240-2) 4.3 Interface description Figure 4-2 PM240-2, frame size FSB (view from below and front) Figure 4-3 PM240-2, frame size FSC (view from below and front) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 75
PM240-2, frame size FSD (view from below and front) Note Use of the safety function "STO" via PM terminals with SINAMICS S110 With enabled Safety Integrated functions of the CU305, a simultaneously active STO function via PM terminals causes error messages to be output (see Chapter STO connection via PM terminals (Page 82)).
Page 76
PM240-2, frame size FSE (view from below and front) Note Use of the safety function "STO" via PM terminals with SINAMICS S110 With enabled Safety Integrated functions of the CU305, a simultaneously active STO function via PM terminals causes error messages to be output (see Chapter STO connection via PM terminals (Page 82)).
Line conductor L2 Line conductor L3 PE connection Power Modules PM240-2: FSD and FSE Table 4- 3 Line supply connection terminal Terminals Signal name Technical data PE connection Line conductor L1 Line conductor L2 Line conductor L3 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Motor phase U Motor phase V Motor phase W Power Modules PM240-2: FSD and FSE Table 4- 5 Motor terminals Terminal Signal name Technical data PE connection Motor phase U Motor phase V Motor phase W SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Power Modules PM240-2: FSE Table 4- 9 DC link terminals Terminal Signal name Technical data DC link negative DC link positive SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Connector Terminal Designation Technical data Low signal Safe Brake Relay to PM240-2 High High signal Safe Brake Relay to PM240-2 Note You will find more information in Chapter Option module Safe Brake Relay (Page 208). SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
For the Power Modules PM240-2 with frame sizes FSD and FSE, this functionality can be implemented in the hardware via the PM terminals STO_A/STO_B. However, with SINAMICS S110, "Safe Torque Off" via PM terminals can only be used if the Safety Integrated functions of the CU305 are deactivated.
Depth [mm] Power Module Shield plate at Shield plate at Total the top the bottom 83.5 707.5 122.5 849.5 Figure 4-7 Dimension drawing of PM240-2 Power Modules, frame size FSA, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 84
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-8 Dimension drawing of PM240-2 Power Modules, frame size FSB, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 85
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-9 Dimension drawing of PM240-2 Power Modules, frame size FSC, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 86
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-10 Dimension drawing of PM240-2 Power Modules, frame size FSD, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 87
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-11 Dimension drawing of PM240-2 Power Modules, frame size FSE, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 88
The Power Modules can be mounted side by side. For tolerance reasons, we recommend a lateral clearance of 1 mm. For PT modules, the maximum wall thickness of the cabinet is 3.5 mm. Figure 4-12 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSA, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 89
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-13 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSB, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 90
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings Figure 4-14 Dimension drawing of PM240-2 Push Through Power Modules, frame size FSC, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Blocksize Power Modules (PM240-2) 4.4 Dimension drawings 4.4.2 Drilling patterns Power Modules frame sizes FSA / FSB / FSC Figure 4-15 Drilling patterns of PM240-2 Power Modules, frame sizes FSA, FSB, FSC; all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 92
Drilling patterns of PM240-2 Power Modules, frame sizes FSD, FSE; all data in mm and (inches) Power Modules, Push Through, frame sizes FSA / FSB / FSC Drilling patterns for Power Modules, Push Through, FSA - FSC, see Chapter Mounting rack/dimension drawings. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
This mounting frame includes the necessary seals and frame to ensure compliance with degree of protection IP54. If you do not use the mounting frames, you must ensure that the required degree of protection is complied with using other appropriate measures. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
411 x 200 x 171 500 x 200 x 171 8 x M5 studs, 3.5 Nm with 8 x M5 nuts, washers Inch 16.18 x 7.87 x 6.73 19.69 x 7.87 x 6.73 8 x M5 washers inserted SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Tools required: ● Torx screwdriver T20 Figure 4-17 Mounting the shield connection plate on Power Modules PM240-2 FSA, FSB, and FSC Figure 4-18 Mounting the shield connection plate on Power Modules PM240-2 FSD and FSE SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
IP55 using a suitable mounting frame and seals, the Power Modules also comply with this degree of protection. According to UL, the Power Modules meet the requirements for an open type component, external type 12. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0.02 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 98
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0,045 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 99
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0.075 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 101
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0.02 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 102
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0,045 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 103
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power Module with an external line filter class B and a motor reactor. Power loss in the cabinet: 0.075 kW. The remaining power loss is dissipated through the heat sink. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 104
) for a line impedance corresponding to u = 1%. rated To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 150 m (shielded) it the max. motor cable length. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 105
) for a line impedance corresponding to u = 1%. rated To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 150 m (shielded) it the max. motor cable length. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
You will find the derating characteristics in Chapter Derating (Page 31). Overload capability Figure 4-20 Duty cycle with initial load (for servo drives) Figure 4-21 Duty cycle without initial load (for servo drives) Figure 4-22 S6 duty cycle with initial load (for servo drives) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 107
Figure 4-25 Duty cycle with 30 s overload with a duty cycle duration of 300 s Note The short leading edges of the duty cycles shown can only be achieved using speed or torque control. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 108
Blocksize Power Modules (PM240-2) 4.6 Technical data SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
A thermostatic switch monitors the braking resistor for overtemperature and issues a signal on an isolated contact if the limit value is exceeded. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
• In addition, apply one of the following measures: – Using cables with double insulation. – Observe adequate clearances, e.g. through the use of spacers. – Route the cables in separate cable ducts or pipes. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Connect the thermostatic switch to a free digital input of the Control Unit. Set the function of this digital input to the OFF2 command. If the braking resistor overheats, the Power Module is disconnected from the power supply. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Connecting the thermostatic switch on the braking resistor to a Control Unit 5.2.4 Dimension drawings Braking resistors for PM240-2 Power Modules Figure 5-2 Dimension drawing of braking resistor for PM240-2, frame size FSA, 0.55 … 1.5 kW, all dimensions in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 113
Dimension drawing of braking resistor for PM240-2, frame size FSA, 2.2 … 3.0 kW, all dimensions in mm and (inch) Figure 5-4 Dimension drawing braking resistor for PM240-2, frame size FSB, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 114
DC link components 5.2 Braking resistors Figure 5-5 Dimension drawing of PM240-2, frame size FSC, all data in mm (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The PE conductor in the pigtail is, in this case, not to be used, but can be suitably tied off or cut off. For frame sizes FSD and FSE, PE connection of the braking resistor is achieved via the shield connection plate above terminals R1 and R2. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Frame size Unit rating of the Power Module 0.55 … 0.75 1.1 … 2.2 3.0 … 4.0 x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 117
Braking resistors for Blocksize PM240-2, 400 V, FSD - FSE Article No. 6SE6400- 4BD21-2DA0 4BD22-2EA1 4BD24-0FA0 Resistance Ω Unit rating P Peak power P Load duration for peak power T Period duration of braking duty cycle Degree of protection IP20 IP20 IP20 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 118
Load diagram for the braking resistor, in Blocksize format T [s]: Period duration of braking duty cycle [s]: Duration of load with peak power [kW]: Unit rating of the braking resistor [kW]: Peak power of the braking resistor SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Further, increased failures can occur and the service life of units/systems may be shortened. • It is essential that you maintain 100 mm ventilation clearances above and below the component. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 120
There is a risk that the motor reactor will be thermally damaged. • Use only motor reactors that have been approved for SINAMICS by Siemens. NOTICE Damage to the motor reactor if the maximum output frequency is exceeded The maximum permissible output frequency when motor reactors are used is 150 Hz.
Power components on the motor side 6.1 Motor reactors 6.1.3 Dimension drawings Motor reactors 6SL3202-0AE16-1AC0 and 6SL3202-0AE18-8CA0 for PM240-2, FSA or FSB Figure 6-1 Dimension drawing motor reactors for PM240-2, FSA or FSB, all data in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 122
Power components on the motor side 6.1 Motor reactors Motor reactors 6SL3202-0AE21-8AC0 for PM240-2, FSB or FSC Figure 6-2 Dimension drawing motor reactors for PM240-2, FSB or FSC, all data in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 123
Power components on the motor side 6.1 Motor reactors Motor reactors 6SL3202-0AE23-8AC0 for PM240-2, FSC or FSD Figure 6-3 Dimension drawing motor reactors for PM240-2, FSC or FSD, all data in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 124
Dimension drawing motor reactors for PM240-2, FSD, all data in mm and (inch) Motor reactors 6SE6400-3TC07-5ED0 for PM240-2, FSD or FSE ① PE terminal M6 x 12 Figure 6-5 Dimension drawing motor reactors for PM240-2, FSD or FSE, all data in mm and (inch) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
1PE24-5xL0 1PE26-0xL0 1PE31-1xL0 1PE27-5xL0 1PE28-8xL0 Frame size FSD/FSE Unit rating of the Power Module 30 ... 45 x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 128
Power components on the motor side 6.1 Motor reactors SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
If the safety functions of the Control Unit are not being used, the failsafe digital inputs can be used as 6 additional electrically isolated digital inputs. If the safety functions of the Control Unit are not being used, the failsafe digital input can be used as 1 additional electrically isolated digital input. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Incorrect parameter assignment can cause machines to malfunction, which can lead to injuries or death. • Protect files stored on exchangeable storage media from malicious software using appropriate protection measures, e.g. virus scanners. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 131
Damage caused by the use of unsuitable DRIVE-CLiQ cables If unsuitable DRIVE-CLiQ cables are used, damage or malfunctions can occur in the devices or the system itself. • Use only appropriate DRIVE-CLiQ cables that have been approved by Siemens for the use case in question. Note Functional faults caused by dirty DRIVE-CLiQ interfaces Malfunctions can occur in the system due to use of dirty DRIVE-CLiQ interfaces.
Electronics power supply X130 Fail-safe digital inputs X131 Fail-safe digital inputs/outputs X132 Digital inputs/outputs, analog input X133 Digital inputs, temperature sensor input Encoder interface (HTL/TTL/SSI) Serial interface (RS232) X520 / X521 / X522 Measuring sockets SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
LNKx Missing or faulty link Green Flashing light 0.5 Hz Connection establishment Continuous light 10 or 100 Mbit link available ACTx No activity Yellow Flashing light Data is being received or sent at port x SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
STARTER software is used to change the PROFIBUS factory setting to USS. For operation as a USS interface, only terminals 3, 5, and 8 are used. You will find information on configuration in the SINAMICS S110 Function Manual. 7.3.3.3 PROFIBUS/USS address switch With the CU305 DP, the address switch can be used to set both PROFIBUS addresses and USS addresses.
Page 137
= 64 Setting the PROFIBUS address 1. Setting via the corresponding parameters (see SINAMICS S110 List Manual) – The STARTER is used to set the bus address for a PROFIBUS node to a value between 1 and 126. This is only possible if the address switch is set to 0 or 127 (factory setting).
B track negative B track positive AN_SSI_XDAT A track negative / SSI data negative AP_SSI_DAT A track positive / SSI data positive Connector type 15-pin sub D connector Measuring current via temperature sensor connection: 2 mA SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 141
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect when the motor overheats. Overheating can cause damage to the motor. • Connect a KTY temperature sensor with the correct polarity. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 142
AN_SSI_XDAT, BN, RN not connected to X23 For the relevant parameters for setting the mode, see the SINAMICS S110 List Manual Other signal levels according to the RS422 specification. The absolute level of the individual signals varies between 0 V and V of the measuring system.
Page 143
Connection example 2: HTL encoder, unipolar, with reference signal Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar connection should only be used if the encoder type does not output push-pull signals. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
7.3.5.3 Pulse/direction interface Setpoint value specification with HTL level Thanks to the pulse/direction interface, SINAMICS S110 can be used for simple positioning tasks on a controller. Connection to the controller is via internal encoder interface X23 of the CU305. The controller gives the drive two signals: A pulse sequence with a pulse/pause ratio of 50:50 and a directional signal.
Page 145
Type: 15-pin SUB D connector The required settings for the pulse/direction interface need to be made in the STARTER. Please refer to the SINAMICS S110 Function Manual for details. Connection example The image below shows an example of how to connect TTL encoders to interface X23 of a Control Unit CU305 for setpoint value specification via A track and B track.
Max. cross section that can be connected: 2.5 mm The maximum cable length that can be connected is 30 m. Note The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
An F-DI consists of two digital inputs. The cathode of the optocoupler is additionally connected to one of these. Note An open input is interpreted as "low." Note If M1 is connected to M (X124 or X132), the system is no longer electrically isolated. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The F-DO comprises two digital outputs each connected with an external 24 V supply. Note The fail-safe digital output (DO 16+, DO 16-) switches off retentively in the event of a short- circuit. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The common mode range may not be violated. This means that the analog differential voltage signals can have a maximum offset voltage of ±15 V with respect to the reference potential. If the range is infringed, incorrect results may occur during analog/digital conversion. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Max. cross section that can be connected: 1.5 mm Measuring current via the temperature sensor connection: 2 mA DI: Digital input The maximum cable length that can be connected is 30 m. Note An open input is interpreted as "low." SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Ground for measuring sockets Continued-short-circuit-proof The measuring sockets are only suitable for bunch pin plugs with a diameter of 2 mm. Note The measuring sockets support commissioning and diagnostic functions. It must not be connected for normal operation. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Incorrect parameter assignment can cause machines to malfunction, which can lead to injuries or death. • Protect files stored on exchangeable storage media from malicious software using appropriate protection measures, e.g. virus scanners. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 153
The memory card may only be inserted as shown in the figure (arrow top right). Working with the memory card If you return a defective CU305 to Siemens, remove the memory card and keep it in a safe place. When you commission the replacement device, all stored data (firmware, licenses, parameters) will be available to you again.
CU305 Control Units 7.4 Connection examples Connection examples Connection examples without a safety function Figure 7-9 Internal connections of the CU305 without the safety function SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 155
CU305 Control Units 7.4 Connection examples Figure 7-10 Example of circuits for the DI/DO without the safety function SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 156
CU305 Control Units 7.4 Connection examples Connection example with a safety function Figure 7-11 Connection example, CU305 with safety function You will find more information about connections in the manual: SINAMICS S110 Function Manual, Drive Functions SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The system is ready to operate when the "RDY" LED lights up green permanently. All the LEDs are controlled by the software loaded during operation (see Behavior of the LEDs in the operating state (Page 159)). SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Firmware update from memory card Status Comment OUT>5V Orange Firmware update COM-LED flashing without specific flashing frequency Red 2 Hz Firmware update Check whether the memory failed card is inserted or replace the memory card. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Waiting for POWER ON of the corre- nent. sponding component. Green/ 2 Hz Recognition of components via LED is activat- Orange flashing light Note: Red/ Both options depend on the LED status when Orange activated. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 160
Continuous light The voltage of the electronics power supply for the measuring system is 24 V. Operating state (reserved) For activation of component recognition via LED, see the SINAMICS S110 List Manual Possible causes: - The controller is not transferring any setpoints.
• Only connect an encoder to 24 V that is rated for a voltage of 24 V. Dimension drawings 7.6.1 Dimension drawing, CU305 PN Figure 7-12 Dimension drawing of Control UnitCU305 PN, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
CU305 Control Units 7.6 Dimension drawings 7.6.2 Dimension drawing CU305 DP/CAN Figure 7-13 Dimension drawing of Control Unit CU305 DP and CU305 CAN, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Removing the CU305 from the Power Module (frame size FSA) To remove the Control Unit from the Power Module, press the blue release lever, shown in the diagram, downward and swing the Control Unit out to the front. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Current 0.35 PE/ground connection On the housing with M4 screw Tightening torque: 3 Nm Response time The response time of digital inputs/outputs depends on the evaluation (see SINAMICS S110 List Manual, Function Diagrams). Weight 0.95 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
SINAMICS Control Unit and operated. The following functions are possible with the BOP: ● Input of parameters and activation of functions ● Display of operating modes, parameters, alarms and faults 8.1.2 Interface description Figure 8-1 Basic Operator Panel BOP20 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 166
P key. Is light (bright) if at least one parameter was changed and the calculation for con- sistent data management has still not been initiated. Below, Displays, e.g. parameters, indices, faults and alarms. 6 position SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 167
The effectiveness of this key to acknowledge faults can be defined using the appropriate BICO parameterization. Parameter The meaning of these keys depends on the actual display. Raise The keys are dependent on the actual display and are used to raise or lower values. Lower SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Mounting The photographs show how to mount the Basic Operator Panel BOP20 on a CU305. 1. BOP20 and Control Unit CU305 2. Press the latching cams of the cover together simultane- ously. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 169
2. Keep the latching cams pressed together and pull the BOP20 straight out. 3. Insert the blanking cover. Displays and operator controls of the BOP20 You will find information on the displays and operator controls of the BOP20 in the SINAMICS S110 Function Manual. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
When opening plug connections in operation, arcs can result in severe injury or death. • Disconnect or connect the encoder cables to Siemens motors, which are not expressly released for connecting and disconnecting during operation, in a deenergized condition only.
Page 171
Damage caused by the use of incorrect DRIVE-CLiQ cables The use of incorrect or not released DRIVE-CLiQ cables can cause damage or functional faults to devices or the system. • Use only appropriate DRIVE-CLiQ cables that have been approved by Siemens for the use case in question. Note...
Reserved, do not use Reserved, do not use M (0 V) Electronics ground Connector DRIVE-CLiQ socket type The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery. Blanking covers (50 x) Article No:: 6SL3066-4CA00-0AA0 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Temperature sensor KTY84-1C130 / PTC Connector type: 25-pin SUB D connector Measuring current via temperature sensor connection: 2 mA Accuracy of temperature measurement: - KTY: ±7 °C (incl. evaluation) - PTC: ±5 °C (incl. evaluation) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Max. cross section that can be connected: 2.5 mm² The maximum cable length that can be connected is 30 m. Note The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Red/ orange See SINAMICS S110 List Manual for the parameters to activate component recognition via LED Cause and rectification of faults The following documents contain information about the cause of faults and how they can be rectified: ●...
Supplementary system components and encoder system integration 8.2 Sensor Module Cabinet-Mounted SMC10 8.2.5 Dimension drawing Figure 8-4 Dimension drawing of the Sensor Module Cabinet SMC10, all dimensions in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
1. First shift the mounting slide downwards at the lug to release the interlocking with the mounting rail. 2. Swivel the component to the front and withdraw it upwards from the DIN rail. ① Mounting slide ② Mounting rail Figure 8-5 Removing from a DIN mounting rail SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
15000 rpm 7500 rpm The ratio between the ohmic resistance R and the inductance L (the primary winding of the resolver) determines whether the resolver can be evaluated with the SMC10. See the following diagram: SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 180
Rotor impedances that can be connected with excitation frequency f = 5000 Hz To check as shown in the figure above, the impedances Z or Z (impedance between R1 and R2 with short-circuited or open outputs) from the encoder manufacturer's data sheet must be used. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Danger to life due to failure to heed the specific safety instructions for Sensor Modules Failure to heed the Specific safety instructions for Sensor Modules (Page 170) can result in accidents causing severe injuries or death. • Heed the Specific safety instructions for Sensor Modules. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Reserved, do not use Reserved, do not use M (0 V) Electronics ground Connector DRIVE-CLiQ socket type The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery. Blanking covers (50 x) Article No:: 6SL3066-4CA00-0AA0 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Temperature sensor KTY84-1C130 / PTC Connector type: 25-pin SUB D connector Measuring current via temperature sensor connection: 2 mA Accuracy of temperature measurement: - KTY: ±7 °C (incl. evaluation) - PTC: ±5 °C (incl. evaluation) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Max. cross section that can be connected: 2.5 mm² The maximum cable length that can be connected is 30 m. Note The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Red / Orange See SINAMICS S110 List Manual for the parameters to activate component recognition via LED Cause and rectification of faults The following documents contain information about the cause of faults and how they can be rectified: ●...
Supplementary system components and encoder system integration 8.3 Sensor Module Cabinet-Mounted SMC20 8.3.5 Dimension drawing Figure 8-8 Dimension drawing of the Sensor Module Cabinet SMC20, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
1. First shift the mounting slide downwards at the lug to release the interlocking with the mounting rail. 2. Swivel the component to the front and withdraw it upwards from the DIN rail. ① Mounting slide ② Mounting rail Figure 8-9 Removing from a DIN mounting rail SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Current controller clock cycle For a current controller cycle clock of 31.25 µs, use an SMC20 with Article No. 6SL3055- 0AA00-5BA3. Figure 8-10 Maximum cable lengths depending on the SSI baud rate for SSI encoders SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Danger to life due to failure to heed the specific safety instructions for Sensor Modules Failure to heed the Specific safety instructions for Sensor Modules (Page 170) can result in accidents causing severe injuries or death. • Heed the Specific safety instructions for Sensor Modules. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Reserved, do not use Reserved, do not use M (0 V) Electronics ground Connector DRIVE-CLiQ socket type The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery. Blanking covers (50 x) Article No:: 6SL3066-4CA00-0AA0 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Overheating can cause damage to the motor. • Connect a KTY temperature sensor with the correct polarity. Details on the parameterization of the KTY temperature sensor can be found in the SINAMICS S110 Function Manual. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 194
• Only use temperature sensors that fully comply with the specifications of the safety isolation. • If safe electrical separation cannot be guaranteed (for linear motors or third-party motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal Module TM120. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Danger to life through electric shock due to unconnected cable shields Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected cable shields. • Attach the cable shield to the component for the encoder system connection at the terminals. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 196
• Connect a KTY temperature sensor with the correct polarity. Details on the parameterization of the KTY temperature sensor can be found in the SINAMICS S110 Function Manual. Note The maximum length of the temperature sensor cable is 100 m. The cables must be shielded.
Connection examples Connection example 1: HTL encoder, bipolar, with reference signal Figure 8-12 Connection example 1: HTL encoder, bipolar, with reference signal Signal cables must be twisted in pairs to improve immunity to induced noise. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 198
The unipolar connection should only be used if the encoder type does not output push-pull signals. Figure 8-14 Photo of connection example 2: SMC30, 30 mm wide The photo above shows the wire jumpers for connecting unipolar HTL encoders with a reference signal. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Power supply > 5 V Data on the parameters for activating the component recognition via LED, see SINAMICS S110 List Manual NOTICE Damage to the encoder electronics due to incorrect voltage supply If an encoder that is designed for a 5 V supply is operated with a 24 V supply, this can destroy the encoder electronics.
Supplementary system components and encoder system integration 8.4 Sensor Module Cabinet-Mounted SMC30 8.4.6 Dimension drawing Figure 8-15 Dimension drawing of the Sensor Module Cabinet SMC30, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
1. First shift the mounting slide downwards at the lug to release the interlocking with the mounting rail. 2. Swivel the component to the front and withdraw it upwards from the DIN rail. ① Mounting slide ② Mounting rail Figure 8-16 Removing from a DIN mounting rail SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
If the correct shielding procedures or the permissible cable lengths are not observed, it can cause damage or the machine may malfunction. • Only use shielded cables. • Do not exceed the cable lengths stated in the technical data. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
High signal level Hdiff (HTL bipolar) Low signal level Ldiff (HTL bipolar) High signal level Hdiff (SSI bipolar at X520 or X521/X531) Low signal level Ldiff (SSI bipolar at X520 or X521/X531) Signal frequency Edge clearance SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 204
(only for 5 V encoder system power supply). SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 205
The unipolar connection should only be used if the encoder type does not output push-pull signals. See the diagram "Maximum cable length depending on the SSI baud rate for SSI encoders" SSI encoder Figure 8-18 Maximum cable lengths depending on the SSI baud rate for SSI encoders SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 206
For encoders with a 5 V supply at X521/X531, the cable length depends on the encoder current (for 0.5 mm conductor cross sections): Figure 8-19 Max. cable length as a function of the encoder current drawn SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 207
100 m max. because the voltage drop depends on the cable length and the encoder current. Figure 8-20 Signal characteristic of track A and track B between two edges: Time between two edges with pulse encoders Figure 8-21 Position of the zero pulse to the track signals SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
• Set the DC power supply to 26 V. This ensures that the power supply for the brake remains within the permissible range when the following conditions are met: – Use of Siemens three-phase motors – Use of Siemens MOTION-CONNECT power cables – Motor cable lengths: max. 100 m SINAMICS S110...
Max. cross section that can be connected: 2.5 mm² The maximum cable length that can be connected is 30 m. Note The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Current requirement, max. Motor brake at 24 V DC 0.05 + current requirement of the motor brake Conductor cross section, max. Dimensions (W x H x D) 69 x 63 x 33 Weight approx. 0.17 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 212
Supplementary system components and encoder system integration 8.5 Option module Safe Brake Relay SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The use of incorrect or not released DRIVE-CLiQ cables can cause damage or functional faults to devices or the system. • Use only appropriate DRIVE-CLiQ cables that have been approved by Siemens for the use case in question. SINAMICS S110...
Dimension drawing of the DRIVE-CLiQ cabinet gland, all dimensions in mm and (inches) ① Cabinet panel ② Flange, SW18 Figure 9-4 Dimension drawing of the DRIVE-CLiQ cabinet bushing M12, all dimensions in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
In order to install the DRIVE-CLiQ cabinet gland, you must make a cutout in the control cabinet panel as shown in the diagram below. Figure 9-5 Cutout in the control cabinet, all dimensions in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 217
① Control cabinet panel ② M3 screw, tightening torque 0.8 Nm ③ DRIVE-CLiQ cabinet bushing Figure 9-6 Installing the DRIVE-CLiQ cabinet bushing for cables with DRIVE-CLiQ connectors SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Mounting from the outside using an O ring that can be screwed ① Threaded hole with chamfer Figure 9-8 Threaded hole for mounting the DRIVE-CLiQ cabinet bushing M12 with an O-ring that can be screwed from the outside SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Table 9- 1 Technical data of DRIVE-CLiQ cabinet bushings Unit 6SL3066-2DA00-0AA0 6FX2003-0DT67 DRIVE-CLiQ Weight 0.165 0.035 Degree of protection IP54 outside the control cabinet IP67 according to IP20 or IPXXB inside the con- EN 60529 trol cabinet SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Damage caused by the use of incorrect DRIVE-CLiQ cables The use of incorrect or not released DRIVE-CLiQ cables can cause damage or functional faults to devices or the system. • Use only appropriate DRIVE-CLiQ cables that have been approved by Siemens for the use case in question. 9.2.3 Interface description 9.2.3.1...
Accessories 9.2 DRIVE-CLiQ coupling 9.2.4 Dimension drawing Figure 9-11 Dimension drawing of the DRIVE-CLiQ coupling, all dimensions in mm and (inches) 9.2.5 Mounting ① Contact surface Figure 9-12 Hole drilling pattern for installation SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Degree of protection IP67 acc. to EN 60529 Mounting frame 9.3.1 Description With the use and proper installation of Siemens mounting frames, the Power Modules Push Through achieve degree of protection IP55. Article Nos. ● FSA: 6SL3260-6AA00-0DA0 ● FSB: 6SL3260-6AB00-0DA0 ●...
Accessories 9.3 Mounting frame 9.3.2 Dimension drawings Dimension drawings of mounting frame, frame sizes FSA to FSC Figure 9-13 Dimension drawing of mounting frame, frame size FSA and FSB, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 224
Accessories 9.3 Mounting frame Figure 9-14 Dimension drawing of mounting frame, frame size FSC, all data in mm and (inches) SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
2. Fasten the mounting frame to the outer wall of the cabinet. Tighten the 2 screws finger- tight. 3. Attach the seal to the inner side of the cabinet. 4. Fasten the Power Module. Tighten the screws finger-tight. 5. Tighten all screws with a torque of 3.5 Nm. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Electrical equipment of machines Part 1: General requirements All information for device selection in this section applies to: ● Operation in a TN system ● Operating voltage range from 1-phase 200 VAC to 3-phase 440 VAC SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Fire hazard due to overheating when permissible cable lengths are exceeded Excessively long power cables can cause overheating of components with resulting fire and smoke development. • The cable lengths (e.g. motor cable, DC-link cable) listed in the technical data must not be exceeded. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
● SINAMICS line filter ● Observance of information about cable shielding and equipotential bonding ● Only the recommended Siemens power and signal cables are used ● Only cables from Siemens may be used for DRIVE-CLiQ connections You will find MOTION-CONNECT cables in catalog PM21.
The cable shields must be connected as close to the conductor terminal connections as possible to ensure a low-impedance connection with cabinet ground. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 231
Signal cables (shielded and unshielded) connected to the drive line-up must be laid at a great distance from strong external magnetic sources (e.g. transformers, line reactors). In both cases, a distance of ≥ 300 mm is usually sufficient. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
– Using the digital outputs CU305 2. The electronics of Sensor Modules 3. The Safe Brake Relay (motor holding brakes) Other loads must only be connected to these power supply units if they are separately protected from overcurrent. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 233
The DC power supply should be set to 26 V. This ensures that the power supply for the brake remains within the permissible range when the following conditions are fulfilled: • Use of Siemens three-phase motors • Use of Siemens MOTION-CONNECT power cables • Motor cable lengths: max. 100 m SINAMICS S110...
● Cable routing method according to EN 60204-1 The overcurrent protection devices can be determined according to EN 60204-1, Section 14. Circuit-breakers from Siemens Catalogs LV 1 and LV 1T are recommended as overcurrent protection devices on the primary side.
Typical 24 V current consumption of the components A separate 24 V power supply must be used for the SINAMICS S110 drive line-up. The following table can be used to calculate the 24 V DC power supply. The values for typical current consumption are used as a basis for configuration.
3-phase 380 V AC -10 % (-15 % < 24 6SL3100-1DE22-0AAx < 1 min) to 480 V AC +10% DC 300 … 800 You will find more information on power supply units in catalogs PM21 and NC61. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Copper cables with appropriate cross sections (>2.5 mm²) must be used for the ground connection of PROFIBUS nodes. For more information about grounding PROFIBUS, see: http://www.profibus.com/fileadmin/media/wbt/WBT_Assembly_V10_Dec06/start.html SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 238
Failure to heed the information provided above for functional equipotential bonding can cause the faults in devices and disturb fieldbus interfaces. Note PROFINET You will find installation guidelines and information on protective grounding and equipotential bonding for all PROFINET types and topologies under DOWNLOADS at: http://www.profibus.com SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
If filtered fans, heat exchangers, or air conditioners are used, you must ensure that the air is flowing in the right direction. You must also ensure that the warm air can escape at the top. The ventilation clearance above and below must be ensured. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 241
• Ensure that the cooling air flow is not blocked by other devices or mix with the exhaust air from other devices. If necessary, insert air baffles. ① Cooling unit ② Cabinet Figure 10-3 Examples of cabinet ventilation SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
– 1/3 AC 200 ... 240 V with permissible deviation – 3 AC 380 ... 480 V with permissible deviation ● Rated pulse frequency of the Power Modules ● Operating components at their unit rating SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
24.0 A / 2.2 kW 1/3 AC 200 … 240 V 0.12 35.9 A / 3.0 kW 1/3 AC 200 … 240 V 0.14 43.0 A / 4.0 kW 1/3 AC 200 … 240 V 0.18 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
3-phase 380 … 480 V AC 0.11 45 A 3-phase 380 … 480 V AC 0.20 90 A FSD/FSE 3-phase 380 … 480 V AC 0.27 178 A 3-phase 380 … 480 V AC 0.47 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
If the auxiliary 230 VAC supplies are present, then a hazardous voltage is present at the components even when the main switch is in the open state. Death or serious injury can result when live parts are touched. • Disconnect the existing auxiliary supply circuits from the supply. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
1. Switch-off the inverter, and wait 5 minutes until the DC link capacitors have been discharged. 2. Withdraw the line and motor cable connectors and, if available, remove the braking resistor from the Power Module. 3. Remove the shield plate from the Power Module. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 247
2. Pull the fan module out of the Power Module. No tools are required for this. Pulling out the fan module also disconnects the electrical connections. Figure 11-2 Removing the fan from PM240-2 FSD and FSE 3. Install the new fan module in the inverse sequence. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
When DC link capacitors are formed, a defined voltage is connected to them and a defined current flows so that the appropriate capacitor characteristics are restored for them to be re- used as DC link capacitors. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 249
Alternatively, use 2 resistors of 1 kΩ / 100 W each (e.g. GWK150J1001KLX000 from Vishay) instead of the incandescent lamps. ● Sundry accessories, such as lamp socket, etc. Figure 11-3 Forming circuit for 3-phase AC Power Modules with incandescent lamps SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 250
Service and maintenance 11.3 Forming the DC link capacitors Figure 11-4 Forming circuit for 3-phase AC Power Modules with resistors Figure 11-5 Forming circuit for 1-phase AC Power Modules with resistors SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
The products described in this Equipment Manual are extensively recyclable on account of the low-toxic composition of the materials used. To recycle and dispose of your old device in an environmentally friendly way, please contact a company that disposes of electronic waste. SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 252
Service and maintenance 11.5 Recycling and disposal SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
0.2 … 2.5 mm Flexible with end sleeve with plastic sleeve 0.2 … 1.5 mm AWG/kcmil 22 … 12 Stripped lengths 6 … 7 mm Tool Screwdriver 0.5 x 3 mm Tightening torque 0.4 to 0.5 Nm SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Sensor Module Cabinet-Mounted SMC10, 170 Forming the DC-link capacitors, 248 Sensor Module Cabinet-Mounted SMC20, 181 Fuse, 36 Sensor Module Cabinet-Mounted SMC30, 190 DC link, 109 Connection Braking resistors in Blocksize format, 111 Line reactors, 56 Motor reactors, Blocksize, 126 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...
Page 266
Cabinet design, 228 Braking resistors in Blocksize format, 115 Line filter, 43 Control Unit CU305 PN, 163 Line reactors, 52 CU305 CAN Control Unit, 163 Motor reactors, 119 CU305 DP Control Unit, 163 Power Modules, 70 SINAMICS S110 Manual, 07/2015, 6SL3097-4AC10-0BP5...