F01107
CU: Data save in the non-volatile memory unsuccessful
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save in the non-volatile memory was not able to be successfully carried out.
- non-volatile memory is defective.
- insufficient space in the non-volatile memory.
Fault value (r0949, decimal interpretation):
Only for internal Siemens troubleshooting.
Remedy:
- try to save again.
- replace the memory card or Control Unit.
F01112
CU: Power unit not permissible
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, decimal interpretation):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
F01120 (A)
Terminal initialization has failed
Message value:
%1
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software error occurred while the terminal functions were being initialized.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01122 (A)
Frequency at the measuring probe input too high
Message value:
%1
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The frequency of the pulses at the measuring probe input is too high.
Fault value (r0949, decimal interpretation):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
8: DI/DO 13 (X132.8)
16: DI/DO 14 (X132.10)
32: DI/DO 15 (X132.11)
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-989