Faults and alarms
List of faults and alarms
F30061 (A)
Bypass contactor monitoring
Message value:
Fault cause: %1 bin
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
At the end of the monitoring time (p0255[1]), the actual state of the bypass contactor does not match the desired
state.
Fault value (r0949, interpret bitwise binary):
Bit 0: Monitoring time exceeded.
Bit 1: Contactor opened during operation.
Bit 2: Contactor closed in OFF state.
Remedy:
- check the monitoring time setting (p0255[1]).
- check the contactor wiring and activation.
- replace the contactor.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F30070
Cycle requested by the power unit module not supported
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A cycle is requested that is not supported by the power unit.
Fault value (r0949, interpret hexadecimal):
0: The current control cycle is not supported.
1: The DRIVE-CLiQ cycle is not supported.
2: Internal timing problem (clearance between RX and TX instants too low).
3: Internal timing problem (TX instant too early).
Remedy:
The power unit only supports the following cycles:
62.5 µs, 125 µs, 250 µs and 500 µs
For fault value = 0:
Set a permitted current control cycle.
For fault value = 1:
Set a permitted DRIVE-CLiQ cycle.
Re fault value = 2, 3:
Contact the manufacturer (you may have an incompatible firmware version).
F30071
No new actual values received from the power unit module
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The number of actual value telegrams from the power unit module that have failed has exceeded the permissible
number.
Remedy:
Check the interface (adjustment and locking) to the power unit module.
F30072
Setpoints are no longer being transferred to the power unit
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The following applies for CU31x and CUA31:
More than one setpoint telegram was not able to be transferred to the power unit module.
Remedy:
The following applies for CU31x and CUA31:
Check the interface (adjustment and locking) to the power unit module.
3-1140
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3