Siemens SINAMICS S110 List Manual page 1163

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

A30804 (F)
Power unit: CRC
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
CRC error actuator
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
Reaction upon F:
OFF2 (OFF1, OFF3)
Acknowl. upon F:
IMMEDIATELY
F30805
Power unit: EPROM checksum error
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.
F30809
Power unit: Switching information not valid
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For 3P gating unit:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
A30810 (F)
Power unit: Watchdog timer
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
When booting it was detected that the cause of the previous reset was an SAC watchdog timer overflow.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
Reaction upon F:
NONE (OFF2)
Acknowl. upon F:
IMMEDIATELY
F30850
Power unit: Internal software error
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred in the power unit.
Fault value (r0949, decimal interpretation):
Only for internal Siemens troubleshooting.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1163

Hide quick links: