Siemens SINAMICS S110 List Manual page 1123

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

2: The master no longer interrogated the CAN node status longer than for its "life time". The "life time" is obtained
from the "guard time" (p8604[0]) multiplied by the "life time factor" (p8604[1]).
- bus cable interrupted.
- bus cable not connected.
- incorrect baud rate.
- incorrect bit timing.
- master fault.
Note:
The fault response can be set as required using p8641.
See also: p8604 (CAN node guarding), p8641 (CAN Abort Connection Option Code)
Remedy:
- check the bus cable
- check the baud rate (p8622).
- check the bit timing (p8623).
- check the master.
The CAN controller must be manually restarted with p8608 = 1 after the cause of the fault has been resolved!
See also: p8608 (CAN Clear Bus Off Error), p8622 (CAN bit rate), p8623 (CAN Bit Timing selection)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08701
CAN: NMT state change
Message value:
%1
Drive object:
All objects
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
A CANopen NMT state transition from "operational" to "pre-operational" or after "stopped".
Fault value (r0949, decimal interpretation):
1: CANopen NMT state transition from "operational" to "pre-operational".
2: CANopen NMT state transition from "operational" to "stopped".
Note:
In the NMT state "pre-operational", process data cannot be transferred and in the NMT state "stopped", no process
data and no service data can be transferred.
Remedy:
Not necessary.
Acknowledge the fault and continue operation.
F08702 (A)
CAN: RPDO Timeout
Message value:
-
Drive object:
All objects
Reaction:
OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time of the CANopen RPDO telegram has expired because the bus connection was either interrupted
or the CANopen Master was switched-off.
See also: p8699 (CAN: RPDO monitoring time)
Remedy:
- check the bus cable
- check the master.
- If required, increase the monitoring time (p8699).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A08751
CAN: Telegram loss
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CAN controller has lost a receive message (telegram).
Remedy:
Reduce the cycle times of the receive messages.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents