Faults and alarms
List of faults and alarms
Remedy:
Not necessary.
The message is withdrawn when the test stop is finished.
Note:
SI: Safety Integrated
C30799
SI Motion MM: Acceptance test mode active
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The acceptance test mode is active. The POWER ON signals of the safety-relevant motion monitoring functions can
be acknowledged during the acceptance test using the acknowledgement functions of the higher-level control.
Remedy:
Not necessary.
The message is withdrawn when exiting the acceptance test mode.
Note:
SI: Safety Integrated
N30800 (F)
Power unit: Group signal
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
NONE
Cause:
The power unit has detected at least one fault.
Remedy:
Evaluate the other messages that are presently available.
Reaction upon F:
OFF2
Acknowl. upon F:
IMMEDIATELY
F30801
Power unit DRIVE-CLiQ: Sign-of-life missing
Message value:
Component number: %1, fault cause: %2
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the power unit concerned.
The computing time load might be too high.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 0A hex:
The sign-of-life bit in the receive telegram is not set.
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- remove DRIVE-CLiQ components that are not required.
- de-select functions that are not required.
- if required, increase the sampling times (p0112, p0115).
- replace the component involved.
F30802
Power unit: Time slice overflow
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A time slice overflow has occurred.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
3-1162
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3