- the internal voltage protection cannot be interrupted due to a fault response. If an overcurrent condition occurs dur-
ing the active, internal voltage protection, then this can destroy the Motor Module and/or the motor.
- if the Motor Module does not support the autonomous, internal voltage protection (r0192.10 = 0), in order to ensure
safe, reliable functioning when the line supply fails, an external 24 V power supply (UPS) must be used for the com-
ponents.
- if the Motor Module does support the autonomous, internal voltage protection (r0192.10 = 1), in order to ensure
safe, reliable functioning when the line supply fails, the 24 V power supply for the components must be provided
through a Control Supply Module.
- if the internal voltage protection is active, it is not permissible that the motor is driven by the load for a longer period
of time (e.g. as a result of loads that move the motor or another coupled motor).
Remedy:
Not necessary.
This a note for the user.
A07908
Internal armature short-circuit active
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Motor Module signals that the motor is short-circuited through the power semiconductors (r1239.5 = 1). The
pulses cannot be enabled. The internal armature short-circuit is selected (p1231 = 4):
Remedy:
For synchronous motors, the armature short-circuit braking is activated with binector input p1230 = 1 signal.
See also: p1230 (Armature short-circuit / DC braking activation), p1231 (Armature short-circuit / DC braking config-
uration)
F07909
Internal voltage protection: De-activation only effective after POWER ON
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The de-activation of the internal voltage protection (p1231 not equal to 3) only becomes effective after POWER ON.
The status signal r1239.6 = 1 indicates that the internal voltage protection is ready.
Remedy:
Not necessary.
This a note for the user.
A07910 (N)
Drive: Motor overtemperature
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
KTY:
The motor temperature has exceeded the fault threshold (p0604 or p0616).
PTC:
The response threshold of 1650 Ohm was exceeded.
Alarm value (r2124, interpret decimal):
this is the number of the temperature channel leading to the message.
See also: p0604 (Motor temperature alarm threshold)
Remedy:
- check the motor load.
- check the motor ambient temperature and cooling.
- check PTC or bimetallic NC contact.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Faults and alarms
List of faults and alarms
3-1109